background image

VTR8300 Series Installation Guide

Room Controller with Optional PIR sensor

Commercial and Hotel/Lodging HVAC Fan Coil Applications

CONTENTS

Installation 2

 Location 

2

 Installation 

2

Terminal, Identification and Function 

3

Communication wiring to VC3xxxE Relay Pack 

3

 BACnet

®

 Communication Wiring (if  applicable) 

3

 

Network wiring topology 

3

How to Enter Setup Screen 

4

Setup Screen Display 

4

Specifications 5
Drawing and Dimensions 

6

Version 5

Summary of Contents for VTR8300 Series

Page 1: ...Applications CONTENTS Installation 2 Location 2 Installation 2 Terminal Identification and Function 3 Communication wiring to VC3xxxE Relay Pack 3 BACnet Communication Wiring if applicable 3 Network wiring topology 3 How to Enter Setup Screen 4 Setup Screen Display 4 Specifications 5 Drawing and Dimensions 6 Version 5 ...

Page 2: ...ow switches thermal protections and or an alarm system to protect the entire system against any catastrophic failures Tampering with the devices or unintended application of the devices results in a void of warranty If the equipment is used in a manner not specified by the manufacturer the protection provided by the equipment may be impaired These devices are not serviceable and must be returned t...

Page 3: ...on each side of base 9 Strip each wire 1 4in 0 6cm from end 10 Insert each wire according to wiring chart next page 11 Gently push excess wiring back into hole 12 Gently align cover to top of base and snap in place from bottom Figure 3 13 Install security screw If replacing an existing Line Voltage FCU Controller label the wires before removal of the controller Electronic controls are static sensi...

Page 4: ...ler All other slave units must be VC3xxxE Relay Pack s WITHOUT remote inputs A maximum of 10 VC3xxxE Relay Packs can be used for a single VTR83xxA Room Controller From VTR83xxA to first VC3xxxE Relay Pack Uses existing or new field wires A minimum of 3 wires are required 14 22 Ga Solid or Stranded shield not necessary From first VC3xxxE to all other slave VC3xxxE Relay Pack s Uses existing or new ...

Page 5: ...ctions such as Date Time Humidity Outdoor Temperature Setpoint and others to be enabled or disabled by setting various parameters Time System Status Fan Status Up Arrow Increase Temperature Setpoint Actual Setpoint Down Arrow Decrease Temperature Setpoint Help Language Selection Temperature Units Fan Mode Date Occupancy Status Indoor Temperature Indoor Humidity Outdoor Temperature System Mode Shor...

Page 6: ... 3 seconds to enter setup mode Note If a configuration installer password is activated to prevent unauthorised access to the configuration menu parameters a password entry prompt will appear to prevent access to the device configuration components Discover Mode The Controller will become discoverable on the wireless ZigBee network for 1 minute this button is hidden if ZigBee settings are not confi...