19 | PIR Ready VTR7300 Series-Installation Guide 

 

 

SeqOpera

 Sequence of 

operation 
Default is: 

Sequence #1

 

Selects the initial sequence of operation required by the 
installation type and the application 

 

SYSTEM = 2 PIPES

 

SYSTEM = 4 PIPES

 

0 =   Cooling Only 

Available 

Available 

1 =   Heating Only 

Available 

Available 

2 =   Cooling / Heating 

or 

Cooling With  
Electric Reheat 

Available 

 

Cooling With Electric Reheat 

Available 

 

Cooling / Heating 

3 =   Heating With  

Electric Reheat 

Available 

Not available 

4 =   Electric Reheat Only 

Available 

Not available 

 

For 2 Pipe output applications, the system access is limited 
if RUI 1 is configured for local changeover COS, COC/NC 
or COC/NC. The current water temperature detected by the 
RUI 1 then limits the system mode available for the local 
configuration or network write. 
 
For sequence 2 & 3, set PulsedHt to On to enable pulsed 
electric reheat applications with VR7300B & E  

 

Fan Menu 

Mode button menu 
configuration 
Default is: 

Menu #4 

 

 

Menu displayed are dependent on model used and sequence 
of operation selected 
Auto Mode operation for sequences 2 and 3 is dependent on 
Auto Fan parameter  

0 =   Low-Med-High 

3

 

Speed configuration

 using 3 fan relays ( L-M-H ) 

1 =   Low-High 

2

 

Speed configuration

 using 2 fan relays ( L-H ) 

2 =   Low-Med-High-Auto 

3

 

Speed configuration

 with Auto fan speed mode  

 using 3 fan relays ( L-M-H-A ) 

3 =   Low-High-Auto 

2

 

Speed configuration

 with Auto fan speed mode using  

 2 fan relays ( L-H-A ) 

4 =   On-Auto 

Single Speed

 

configuration

. Auto is for Fan on demand / On 

is On all the time 

 

DHumiLCK 

Dehumidification lockout 
Default value:  

On = Authorized

 

 

Conditional parameter to Humidity models 
VTR735xX5x00(X) 

Typically toggled via the network. 
This variable enables or disables dehumidification based on 
central network requirements from the BAS front end 
 

 

On = Dehumidification Authorized 

 

Off = Dehumidification Not Authorized 
 

Summary of Contents for VTR7300 Series

Page 1: ...rminal Equipment Controller 8 Configuring and Status Display Instructions 8 Status display 8 User Interface 10 Local keypad interface 10 Dual occupied setpoints adjustment 11 Single occupied setpoints...

Page 2: ...radiation 5 Nothing should restrict vertical air circulation to the Terminal Equipment Controller Installation 1 Swing open the Terminal Equipment Controller PCB to the left by pressing the PCB lockin...

Page 3: ...ed and wired for the following o Cooling only o Heating only o Cooling Heating with network or local auto changeover If replacing an existing Line Voltage FCU Thermostat label the wires before removal...

Page 4: ...ic reheat model dependent The VC3xxxX Relay Pack supplies power to the wall VTR73xxA Terminal Equipment Controller The VTR73xxA Controller controls the VC3xxxX Relay Pack s via a simple communication...

Page 5: ...5 PIR Ready VTR7300 Series Installation Guide MODEL CHART...

Page 6: ...adapter o VCM7300T5000B Terminal Equipment Controller BACnet MS TP communication adapter TERMINAL IDENTIFICATION AND FUNCTION TERMINAL IDENTIFICATION ALL VTR73XXA5X00 X TERMINAL EQUIPMENT CONTROLLER T...

Page 7: ...not necessary Connect only wires 1 Power Common and 2 Tx Rx Communication Network wiring topology VC3XXX LED OPERATION LED Time Status operation Condition of the Status LED Cause Solution 2 short bli...

Page 8: ...ause the back light to come on to high level When left unattended for 10 seconds after changes are made the display will resume automatic status display scrolling To activate the back light to high le...

Page 9: ...two alarms can appear at any given time The priority for the alarms are as follows Three status LED s on the Terminal Equipment Controller cover are used to indicate the status of the fan any speed a...

Page 10: ...ailable as per sequence and menu selected Repetitively pressing the button will toggle between all the available modes Available menus are dependent on selected sequence of operation Is used to toggle...

Page 11: ...lectric Reheat Off Heat 4 Electric Reheat Only Off Heat COOLING MODE HEATING MODE OFF MODE AUTO MODE Setpoint presented to user is the setpoint from the last action taken by the Terminal Equipment Con...

Page 12: ...o is for Fan on demand On is On all the time Auto Auto speed fan mode is also offered in heating mode applications it will not have any effect on dehumidification It will strictly be used for noise co...

Page 13: ...t unauthorized access to the configuration menu parameters A default value of 0 will not prompt a password or lock the access to the configuration menu Range is 0 to 1000 Com Addr Terminal Equipment C...

Page 14: ...to 1000 Range 1 to 500 for centralized networked applications using a VWG or a Jace with the wireless stat driver Range 501 to 1000 is for stand alone applications where no VWG or Jace with the wirele...

Page 15: ...ter to 255 means that every configuration parameters will be set manually BI 1 Binary input no 1 configuration Default value None None No function will be associated with the input Input can be used f...

Page 16: ...configuration Default value None None No function will be associated with the input Input can be used for remote network monitoring COC NH Change over dry contact Normally Heat Used for hot cold wate...

Page 17: ...alarm Contact closed Alarm displayed Service a backlit flashing Service alarm will be displayed on the Terminal Equipment Controller LCD screen when the input is energized It can be tied in to the AC...

Page 18: ...ontrol for VC350xE models only Can be used with 2 4 pipes applications On VDC SSR electric heat 10 second pulsed time base modulation for VC340xE models only Can only be used with 2 pipes system only...

Page 19: ...dHt to On to enable pulsed electric reheat applications with VR7300B E Fan Menu Mode button menu configuration Default is Menu 4 Menu displayed are dependent on model used and sequence of operation se...

Page 20: ...Timer value Default 0 0 hours Time delay between the moment when the Terminal Equipment Controller toggles to stand by mode and the time when the Terminal Equipment Controller unoccupied mode and setp...

Page 21: ...is 54 to 100 F 12 0 to 37 5 C Pband Proportional band setting Default is 3 Adjust the proportional band used by the Terminal Equipment Controller PI control loop Note that the default value of 3 0 F...

Page 22: ...Dual Stp Dual Occupied Setpoints Adjustment AttchStp Single Occupied Setpoint Adjustment TOccTime Temporary occupancy time Default value 2 hours Temporary occupancy time with occupied mode setpoints...

Page 23: ...H will represent a higher accuracy of control at the expense of wearing mechanical components faster Range is 3 4 5 6 7 8 C P H CoolNoNc Normally open or close device Default value NC Adjust the type...

Page 24: ...bulk polymer type sensor Reading range from 10 90 R H non condensing 10 to 20 precision is 10 20 to 80 precision is 5 80 to 90 precision is 10 Less than 1 0 yearly typical drift 30 to 95 R H 12 0 to...

Page 25: ...25 PIR Ready VTR7300 Series Installation Guide DRAWING DIMENSIONS Viconics Technologies Inc Tel Fax Toll free www viconics com...

Reviews: