18
Object Name
Object
Type and
instance
BACnet Index
Text
Default value
Anticycle MV63
1 0
minute
2 minutes
2 1
minute
3 2
minutes
4 3
minutes
5 4
minutes
6 5
minutes
DI1 Configuration
MV65
1 None
None
2 RemNSB
3 RemOVR
4 Filter
5 Service
6 Fan
lock
DI2 Configuration
MV66
1 None
None
2 RemNSB
3 RemOVR
4 Filter
5 Service
6 Fan
lock
Proportional Band
MV 67
1
2
2 F
0.6 C
2
2
3
3 F
1.2 C
3
4
4 F
1.7 C
4
5
5 F
2.2 C
5
6
6 F
2.8 C
6
7
7 F
3.3 C
7
8
8 F
3.9 C
Event Display
MV71
1 2
Events
2 Event
2 4
Events
Heating Stages
MV73
1 Analog
Heat
2 Stages
2 1
Stage
3 2
Stages
Cooling Stages
MV74
1 1
Stage
2 Stages
2 2
Stages
Heat Pump Stages
MV75
1 1
Stage
2 Stages
2 2
Stages
Dehumidification
Lockout Functions
MV 92
1 Disabled
N/A
2 Restricted
3 Enabled