cause the Thermostat to operate incorrectly and service calls to correct issues from these being pressed will 
not be covered under warranty 

DEFAULT SETTINGS FOR THERMOSTATS

 

*** Parameters in green need to be set as directed for the sequence to work as expected. 

Parameter

Default value for bedrooms

PswrdSet

0

Com Addr

---

Pan ID

---

Channel

---

GetFrom

0

BI1

None

BI2

None

UI3

COC/NC (contact open = cold water) 

MenuScro

On

AutoMode

On

C or F

C

Lockout

1 (will display "Lockout" when override button pushed)

Pipe No

This parameter will be fixed to 2.0

SeqOpera

1

Fan Menu

4 (Auto)

St-By Tm

4 hrs

Unocc Tm

24 hrs

St-By HT

19.5C

St-By CL

25.5 C

Unocc HT 

17.5C

Unocc CL 

27.5C

heat max 

24C

cool min 

19C

Pband

3 F

Set Type 

Perment

Spt Func

AttchStp

TOccTime 

2 (Unused)

deadband 

2 F

cal RS 

---

aux cont

0