Copyright © VibroSystM Inc., 2011
20
STATE-200 Installation and Field Wiring_Rev. 0
●
6
Model: AD6, AD6T, AD7,
Module casing: Type A
Sensor with voltage (V
DC
) output
AD11, AD11T, AD12, AD12T
+24VDC
IN B Hi
IN B Lo
IN A Hi
IN A Lo
SW
POS
1
OFF
2
OFF
+
-
S h i e l d
*
N o t e * : T o a v o i d g r o u n d l o o p p r o b l e m s , c o n n e c t s h i e l d
t o e a r t h g r o u n d o n o n e e n d o f t h e c a b l e o n l y .
S h i e l d
*
7
Model: AD6, AD6T, AD7,
Module casing: Type A
Sensor with voltage (V
DC
) output and 24VDC input
AD11, AD11T, AD12, AD12T
+24VDC
IN B Hi
IN B Lo
IN A Hi
IN A Lo
SW
POS
1
OFF
2
ON
+24V
C O M
=
S h i e l d
*
N o t e * : T o a v o i d g r o u n d l o o p p r o b l e m s , c o n n e c t s h i e l d
t o e a r t h g r o u n d o n o n e e n d o f t h e c a b l e o n l y .
S h i e l d
*
8
Model: AD14T
Module casing: Type B
3-wire 10
Ω
(CU10) RTD
+24V
DC
IN B Hi
IN B Lo
IN A Hi
IN A Lo
SW
POS
1
OFF
2
OFF
A Fourth Wire must be added and
connected as close to the sensor as possible
An error in the reading may be present but can be
corrected by adding a negative offset
in the ZOOM software setup
S h i e l d
*
N o t e * : T o a v o i d g r o u n d l o o p p r o b l e m s , c o n n e c t s h i e l d
t o e a r t h g r o u n d o n o n e e n d o f t h e c a b l e o n l y .
S h i e l d
*
Summary of Contents for STATE-200
Page 2: ...Copyright VibroSystM Inc 2011 2 STATE 200 Installation Manual_Table of Contents Rev 0...
Page 4: ...Copyright VibroSystM Inc 2011 4 STATE 200 Installation Manual_Table of Contents Rev 0...
Page 12: ...Copyright VibroSystM Inc 2011 12 STATE 200 General Description_Rev 0...
Page 24: ...Copyright VibroSystM Inc 2011 24 Using the STATE 200 Unit Rev 0...
Page 30: ...Copyright VibroSystM Inc 2011 30 Troubleshooting the STATE 200 Unit_Rev 0...