SmartClass Fiber MPOLx

 

Testing MPO/MTP terminated 12-strand fiber 

 
This quick card describes how to use the VIAVI  MPOLx for 

troubleshooting

 

and loss/length MPO fiber 

certification

.   

 
Equipment Requirements: 

 

MPOLx MPO test kit which will include: 

o

 

MPOLP-85(P) 

 MPO Power Meter 

o

 

MPOLS-8x(P) 

 MPO Light Source 

o

 

MPO/MTP FMAE adapter (APC for SM, PC for MM)

 (P versions)

 

o

 

2x unpinned to unpinned Type A launch cords 

o

 

1x pinned to pinned Type A test cord 

o

 

2x MPO mating adapters 

 

The latest SmartClass Fiber firmware 

o

 

To download the latest version visit http://scf.updatemyunit.net 

 

FiberChek PRO software with version 2.02 or newer 

o

 

To download the latest version visit 

http://fcpro.updatemyunit.net/

  

 

MPO Cleaning Tool 

 
Configure the MPOLP-85P for the type of testing you will be performing: 

 

Create and set-up a project on the MPOLP: 

o

 

From home screen press the management icon (left side of touch screen, middle icon). 

o

 

Select projects, press menu button, and select add. 

o

 

Type the name of the project, tap the check mark to save. 

o

 

Add a description, set the label prefix, label index, and auto increment as desired.  

o

 

Press the back button and set the project to Active. 

 

Create and save the test configuration for the Loss/Length test you wish to perform:   

Note: Setup can only be done on the MPOLP and not the MPOLS.

 

o

 

From home screen select Loss/Length. 

o

 

Press the menu button. 

o

 

Select a pre-set test configuration or create a new one as follows: 

 

Select add 

 and name the test configuration 

(e.g. “

SMF 12 Strand Test

”). Select this 

new test configuration and create a setup for a basic loss/length test:  

 

Fiber Type = MM/SM as appropriate  

 

Test Limit 

 Link Validation. Polarity A, Length 100 meters 

 

Cable Name: OM4/OS1 as appropriate 

 

Cable and Connector: as appropriate 

 

Test Reference Method: 1 Jumper 

 

Pass/Fail Fiber Selection: as appropriate 

 

Ensure the Patch Cord Microscope (PCM) settings are correct (if equipped) 

 using 

correct inspection profile (Ribbon, SM or MM (IEC-61300-3-35 Ed. 2.0) ensures the 
correct illumination of the end face.   

 

Adjust the focus and Y axis. Turn auto-center off.  