background image

Ar

t.-Nr

.:

85301221 E1  •  

V

estamatic GmbH  •  Dohrw

eg 27  •  D-41066 Mönchengladbach  •  www

.v

estamatic.com

Subject to modifications.

© Vestamatic GmbH

IF SMI RS-485

Art.-no.:

01 01092811

Installation and Operating Instructions

IF SMI RS-485 LoVo

Art.-no.: 01092810

RS-485 SMI-Interface for 16 SMI LoVo motors.

IF SMI RS-485 230VAC

Art.-no.: 01092811

RS-485 SMI-Interface for 16 SMI motors.

3. Technical data

1/ 7

G

2. Safety precautions

– Contact a professional electrician for installation.
– Check the control system for signs of mechanical damage after

unpacking. If you notice any shipping damage, do not start up

the control system and notify your supplier immediately.

– The control system should only be used for the purpose speci-

fied by the manufacturer (refer to the operating instructions).

Any changes or modifications thereof are not permissible and

will result in loss of all warranty claims.

– If the control unit cannot be operated without presenting a

hazard, it must be switched off and prevented from being

switched on unintentionally.

– Turn off the power supply and prevent it from being switched

on unintentionally before performing work on any windows,

control or sunshades driven by the control system.

Ä

Supply voltage 230VAC:

230VAC, 50 Hz

Impulse voltage withstand level:

2.5 kV

Rated power:

2 W

Operating temperature:

0 °C (32 °F) to +40 °C (104 °F)

Software class:

A

IP class:

IP 54

Degree of contamination:

2

Dimensions (L × W × D):

115 × 115 × 60 mm

Mark of conformity:

p

4. Hardware

SMI is the abbreviation for 

S

tandard 

M

otor 

I

nterface. SMI has been de-

veloped for the connection of intelligent drives for roller shutters and sun

protection systems. SMI enables to transmit telegrams from control

system to the drive and vice versa. With SMI it is possible to combine

products from different sources together. The SMI Interface should spread

high value solutions and promote drives and controls on the market. The

applications in roller shutters and sun protection systems require extreme

robustness and economic efficiency. SMI has been developed to meet

these requirements.

1. What is SMI?

Contents

1. What is SMI?
2. Safety precautions
3. Technical data
4. Hardware

4.1 Overview IF SMI RS-485

4.1.1 RS-485 BUS
4.1.2 Power supply
4.1.3 SMI BUS
4.1.4 Master Up/Down button
4.1.5 Base Address

4.2 Termination RS-485 BUS

5. Protocol

5.1 Message structure
5.2 CRC16 Calculation
5.3 Steer commands

5.3.1

MSG_UP

5.3.2

MSG_DOWN

5.3.3

MSG_STOP

5.3.4

MSG_STEP_UP

5.3.5

MSG_STEP_DOWN

5.3.6

MSG_SET_POS

5.3.7

MSG_SET_TILT

5.3.8

MSG_SET_POS_STEP_UP

5.3.9

MSG_SET_POS_STEP_DOWN

5.3.10 MSG_GOTO_POS1
5.3.11 MSG_GOTO_POS2

5.4 Maintenance commands

5.4.1

MSG_VERSION

5.4.2

MSG_AUTO_ADDR

5.4.3

MSG_GET_SER

5.4.4

MSG_SET_SMIID

5.4.5

MSG_GET_PAR

5.4.6

MSG_GET_POS1

5.4.7

MSG_SET_POS1

5.4.8

MSG_GET_POS2

5.4.9

MSG_SET_POS2

5.5 Status commands

5.5.1

MSG_GETGENSTAT

5.5.2

MSG_GETDETSTAT

6. PC Test Software

6.1 Communication

6.2 Motor Mask based commands

6.3 Motor ID based commands

6.4 General commands

6.5 Send / Receive

7. Wiring diagrams

7.1 IF SMI RS-485 LoVo
7.2 IF SMI RS-485 230VAC

The IF SMI RS-485 can be used for SMI (230VAC) or SMI LoVo applications.

Important:

It is not allowed to use a combination of SMI (230VAC) and

SMI LoVo on the same SMI BUS.

Summary of Contents for IF SMI RS-485 Series

Page 1: ...e SMI has been de veloped for the connection of intelligent drives for roller shutters and sun protection systems SMI enables to transmit telegrams from control system to the drive and vice versa With...

Page 2: ...ave ID LEN Message length without CRC CMD Command byte DATA Optional data bytes CRC16 16 bits checksum LSB first The IF SMI RS 485 module has 4 DIP switches which represents the base address of the mo...

Page 3: ...of steps 1 255 in DOWN direction 1 step is defined as 2 rotation of the output shaft of the SMI motor The IF SMI RS 485 module responds to this request with a general status message MSG_GETGENSTAT Th...

Page 4: ...15 PAR0 1 Index of the motor parameter PLEN Length of parameter 1 2 or 4 bytes Response SID LEN CMND SMIID VAL0 VALn CRC16 SMIID SMI address of motor 0 15 VAL0 n Parameter value 1 2 or 4 bytes in siz...

Page 5: ...16 bit intermediate position 2 5 5 Status commands define MSG_GETGENSTAT 0xA0 define MSG_GETDETSTAT 0xA1 5 5 1 MSG_GETGENSTAT This message requests the general status of the system Message SID LEN CMN...

Page 6: ...ID based com mands The motor you want to address can be selected with the spin edit box in the dark gray part behind Motor ID Motor ID can be set from 0 to 15 Next press a command button like GET_SERI...

Page 7: ...ifications Vestamatic GmbH Art Nr 85301221 E1 Vestamatic GmbH Dohrweg 27 D 41066 M nchengladbach www vestamatic com IF SMI RS 485 7 1 Wiring diagram IF SMI RS 485 LoVo 7 2 Wiring diagram IF SMI RS 485...

Reviews: