2
Press the Learn button.
Refer to Control Panel manual to complete the learn-in process.
Walk Test
After the detector is learnt-in, put the Control Panel into “
Walk Test
” mode, hold the
detector in the desired location, and press the Test button to confirm this location is
within signal range of the Control Panel, refer to Control Panel manual to complete
Walk Test.
When you are satisfied that the detector works in the chosen location, you can
proceed to mounting.
Battery
The detector uses one “CR2”, 3V Lithium battery as its power source.
When low battery is detected, a low battery signal will be sent to the Control Panel
along with regular signal transmissions for the Control Panel to display the status
accordingly.
When the battery is exhausted, the detector will stop all function, the LED will flash
every 4 seconds.
When changing battery, after removing the old battery, press the Learn button twice
to fully discharge before inserting new battery.
Supervision
After installation, the detector will automatically transmit Supervisory signals
periodically to the Control Panel at random intervals of 30 to 50 minutes.
If the Control Panel has not received the signal from the detector for the preset
period of time, the Control Panel will indicate on its display that the particular
detector is experiencing an out-of-signal problem.
Jumper
OFF
(Factory
default)
‐
When
the
jumper
(JP2)
is
set
as
OFF,
the
Supervision
is
enabled.
Jumper
ON
‐
When
the
jumper
(JP2)
is
set
as
ON,
the
Supervision
is
disabled.