background image

VESDA-E VES-A00-P Product Guide

www.xtralis.com

27

4.2.2

Mounting the Detector with the Mounting Bracket

1. Position the mounting bracket (A) to allow sampling pipes (B) and electrical conduit (C) to line up

horizontally with the alignment marks (D) and vertically with the appropriate pipe depth line (Figure 4-17).

l

3/4 inch IPS pipe (1.05 inch OD) should vertically align with the top depth line (E).

l

25mm pipe should vertically align with the bottom depth line (F).

E

F

B

D

A

C

D

Legend

A

Mounting bracket

B

Sampling Pipes

C

Electrical Conduit

D

Pipe alignment marks

E

3/4 inch IPS pipe (1.05 inch
OD) depth

F

25 mm pipe depth

Figure 4-17: Position Mounting Bracket in line with pipes

2. Mark the mounting surface through two keyholes (B) on the mounting surface (Figure 4-18).

A

B

B

Legend

A

Mounting bracket

B

Keyholes

Figure 4-18: Mark keyholes

3. Insert two screws into the mounting surface at marked positions (Figure 4-19).
4. Slide plate onto the mounting screws and tighten them with a screwdriver (B).

A

B

Legend

A

Mounting bracket

B

Screwdriver

Figure 4-19: Tighten screws

Summary of Contents for VESDA-E VES-A00-P

Page 1: ...VESDA E VES A00 P Product Guide VES A00 P 4 Pipes August 2019 Document 33830_02 Part Number 30916 ...

Page 2: ......

Page 3: ...amage Xtralis is not responsible and cannot be held accountable for any liability that may arise due to improper use of the equipment and or failure to take proper precautions Only persons trained through an Xtralis accredited training course can install test and maintain the system Liability You agree to install configure and use the products strictly in accordance with the User Manual and produc...

Page 4: ...ocument Convention Description Bold Used to denote emphasis Used for names of menus menu options toolbar buttons Italics Used to denote references to other parts of this document or other documents Used for the result of an action The following icons are used in this document Convention Description Caution This icon is used to indicate that there is a danger to equipment The danger could be loss o...

Page 5: ... following measures re orientate or relocate the receiving antenna increase the separation between the equipment and receiver connect the equipment to a power outlet which is on a different power circuit to the receiver or consult the dealer or an experienced radio television technician for help FDA This Xtralis product incorporates a laser device and is classified as a Class 1 laser product that ...

Page 6: ...reshold setting that initiates an evacuation signal must be set such that the sensitivity of each sampling hole is more sensitive than 10 m 3 2 ft as determined by the ASPIRE software Product Listings Regional approvals listings and regulatory compliance vary between product models Refer to www xtralis com for the latest product approvals matrix Document 33830_02 Part Number 30916 ...

Page 7: ...iminary System Check 43 5 Configuration 45 5 1 Communication between Xtralis VSC and the detector 45 5 2 Connecting to the Detector 49 5 3 Authentication 52 5 4 Commands 53 5 5 Configuration Options 56 5 6 Factory Default Settings 71 6 Commissioning 75 6 1 AutoLearn Smoke 76 6 2 AutoLearn Flow 77 6 3 Commissioning Smoke Test 77 7 Maintenance 79 7 1 Standby 79 7 2 Open the Door 80 7 3 Replacing the...

Page 8: ...VESDA E VES A00 P Product Guide 2 www xtralis com A 1 VES A00 P Detector Commissioning Configuration 111 A 2 ASPIRE Data 111 A 3 Smoke Test 111 A 4 Air Sampling Test Results 111 B Glossary 113 Index 115 ...

Page 9: ...n air barrier for optics protection l More robust contamination resistance l Four configurable alarm levels per sector and a wide sensitivity range l Flow fault thresholds configurable per port l Long life easy to replace air sample filter l Quiet operation l Advanced remote diagnostics l Area coverage up to 2 000 m 21 520 ft VES A00 P l Up to four inlet pipes l Total maximum pipe length Four pipe...

Page 10: ...VESDA E VES A00 P Product Guide 4 www xtralis com This page is intentionally left blank ...

Page 11: ... then drawn into the smoke detection chamber via the sampling module after first passing through the replaceable filter A further filter provides filtered clean air to protect the optical surfaces inside the detection chamber from contamination The detection chamber uses a short wavelength laser light source in conjunction with photodiodes and advanced imaging technology to achieve optimum respons...

Page 12: ...tton 2 3 1 Status LEDS The VESDA E VES A00 P detector features a range of LED Indicators which illuminate when their respective activation conditions are met LED Symbol Description Fire 2 The Fire 2 LED is lit when the Fire 2 Alarm threshold is reached The LED will flash once per second until the condition is acknowledged Fire 1 The Fire 1 LED is lit when the Fire 1 Alarm threshold is reached The ...

Page 13: ...conds until the DISABLED LED illuminates continuously l To re enable the unit once all alarms and faults have been acknowledged press and hold the button for approximately 4 seconds until the DISABLED LED deactivates continuously l While the detector is disabled any faults or alarms may be acknowledged by pressing this button once The button will not operate if l the detector is disabled through t...

Page 14: ...ield connection Ethernet The Ethernet port is used for configuration and or monitoring purposes It enables direct or routed network connection between the detector and a PC or laptop installed with Xtralis VSC WIFI The WiFi module provides wireless connection of the detector to the building network for the purpose of configuration and secondary monitoring with Xtralis VSC 2 6 VESDAnet A VESDAnet n...

Page 15: ...n Guides Application Notes for sampled air pre conditioning Storage Conditions Non operational l Humidity Dry 95 l Temperature 0 to 85 C l Must not be exposed to sunlight or other radiation sources Sampling Pipe Network l Maximum length per pipe when using four straight pipes l Four pipe VES A00 P 70 m 230 ft l Maximum total pipe length with branches l Four pipe VES A00 P 560 m 1 837 ft l Pipe Mod...

Page 16: ...5 6 on page 71 for the default settings Referencing Reference smoke level source Table 2 2 VES A00 P Detector Specifications continued Table 2 3 Key Software Features Event Log Up to 20 000 events stored on FIFO basis AutoLearn l Minimum 15 minutes l Maximum 15 days 23 hrs 59 minutes l Recommended 14 days Thresholds are automatically changed from the previously set values to the updated values aft...

Page 17: ...0 5 28 E 34 0 1 34 F 34 0 1 34 G 34 0 1 34 H 34 0 1 34 I 26 5 1 04 J 350 05 13 78 K 224 0 8 82 L 230 2 9 06 M 135 48 5 3 N 132 28 5 21 O 28 5 1 12 P 35 0 1 38 Q 45 0 1 77 R 127 0 5 0 S 143 0 5 63 T 26 0 1 02 Figure 2 4 Front top bottom and side dimensions VESDA E VES A00 P Product Guide www xtralis com 11 ...

Page 18: ...VESDA E VES A00 P Product Guide A B C D E F mm inch A 17 5 0 69 B 315 0 12 4 C 17 5 0 69 D 144 99 5 71 E 77 2 3 04 F 3 5 0 1 Figure 2 5 Rear dimensions with Mounting Bracket 12 www xtralis com ...

Page 19: ...ch A 224 0 8 82 B 112 0 4 41 C 40 9 1 61 D 268 39 10 57 E 40 71 1 6 F 20 25 0 8 G 183 5 7 22 H 20 25 0 8 Figure 2 6 Rear Dimensions with hole locations for direct mounting VESDA E VES A00 P Product Guide www xtralis com 13 ...

Page 20: ...VESDA E VES A00 P Product Guide 14 www xtralis com This page is intentionally left blank ...

Page 21: ...rds l Evenly arrange the sampling pipe network over return air grilles l The sampling pipe fits firmly into the tapered detector port DO NOT glue this connection l Allow sufficient movement at the detector to permit pipe removal for maintenance l Keep the exhaust pipe as short as possible to minimize airflow resistance in the pipe l Pipe ends must be made smooth for bonding l Sampling holes must b...

Page 22: ...g Smoke Detection on page iii 3 4 Managing the Exhaust Air Air is expelled from the detector via the exhaust port at the bottom of the unit enclosure The air exhaust port is tapered to accommodate standard pipes of OD 25 mm ID 21 mm and to provide an airtight seal IPS inch pipes 1 05 inch OD require an adaptor VSP 961 as shown in Figure 3 2 If required connect an outlet pipe to the exhaust manifol...

Page 23: ...xtralis com l A 24 VDC Power Supply and backup battery compliant with local fire protection codes and standards l Screws and inserts for the mounting bracket that are appropriate for the installation location l Type A to Type B USB Interface Lead required for initial configuration of the detector Figure 4 1 l Wrist strap for ESD prevention Figure 4 1 Type A to Type B USB Interface Lead 4 1 Prepare...

Page 24: ...r Figure 4 4 noting the location of air sampling pipes and cable entry points Due to the rigid nature of the plastic pipe installation must provide for sufficient movement in all pipework air inlet air exhaust and cable pipes to allow pipe ends to be easily fitted and removed A B Legend A Min 50 mm 2 in below ceiling level B Mounting Bracket The detector can be mounted directly against a wall or o...

Page 25: ...e user interface has the correct orientation The door must be moved to the other side of the fascia to allow access to the electrical sockets and filter This is done as follows 1 Place the detector on a flat surface with the back plate facing down 2 Open the front door and remove the fascia Refer to Sections 7 2 on page 80 and 7 4 on page 84 for further information Figure 4 5 Detector with fascia ...

Page 26: ...ure 4 6 Tabs used to remove top and bottom cover Legend A Top cover retaining tabs B Bottom cover retaining tabs 4 Detach the tethers Figure 4 7 and Figure 4 8 You can leave the cables from the detector to the fascia connected Figure 4 7 Detaching the tethers ...

Page 27: ...A00 P Product Guide www xtralis com 21 Figure 4 8 Detector with tethers detached 5 Detach the front door from the fascia by removing pin A from the hinge Figure 4 9 Figure 4 10 Leave pin B in place do not remove it ...

Page 28: ...VESDA E VES A00 P Product Guide 22 www xtralis com B A Figure 4 9 Removing door hinge pin A Figure 4 10 Detaching door ...

Page 29: ...by doing the following a Leave the fascia upright b Rotate the detector 180 degrees c Rotate the door 180 degrees and place it next to the right side of the fascia 7 Replace the door hinge pin Figure 4 12 Figure 4 13 A 180 o B Figure 4 11 Rotate detector and door and move door to right side of fascia ...

Page 30: ...VESDA E VES A00 P Product Guide 24 www xtralis com Figure 4 12 Replacing the door hinge pin showing correct positioning of door and pin ...

Page 31: ...he door hinge pin Figure 4 14 Correct positioning of door hinge pin when fully in place 8 Re attach the tethers Attach at the slots circled in Figure 4 15 Position the tethers in the slots and pull up as shown in Figure 4 16 Figure 4 15 Re attach tethers at circled positions ...

Page 32: ...overs 10 Re attach the fascia Re attach to the front of the detector by tightening the two retaining screws as shown in Figure 7 8 11 The detector is now inverted The display should be upright while the exhaust vent is at the top and sampling pipe inlets at the bottom The electrical connections and filter should be accessible by opening the door ...

Page 33: ...with the bottom depth line F E F B D A C D Legend A Mounting bracket B Sampling Pipes C Electrical Conduit D Pipe alignment marks E 3 4 inch IPS pipe 1 05 inch OD depth F 25 mm pipe depth Figure 4 17 Position Mounting Bracket in line with pipes 2 Mark the mounting surface through two keyholes B on the mounting surface Figure 4 18 A B B Legend A Mounting bracket B Keyholes Figure 4 18 Mark keyholes...

Page 34: ... slots on the mounting bracket and slide the detector down until the top of the detector is flush with the top of the mounting bracket Figure 4 21 A A A Legend A Mounting buttons Figure 4 21 Mounting the detector 7 Open the door on the front of the detector Figure 4 22 Refer to Section 7 2 on page 80 for further information on how to open the door 8 Insert and tighten the locking screw A This secu...

Page 35: ...nting template 3 Insert two M4 button head screws at positions A and B such that the screw head is protruding 7 mm from the wall Figure 4 24 Drill a pilot hole at position C for later insertion of a screw at Step 12 7mm Upright Detector Inverted Detector 25mm 3 4 IPS 25mm 3 4 IPS Edge of Detector 25m m 3 4 IPS 25m m 3 4 IPS Edge of Dete ctor B A A B C C Figure 4 24 Insert mounting screws 4 Positio...

Page 36: ...ed retract the inlet and exhaust pipes and electrical conduit 10 Mount the detector onto the screws using the keyholes using the following steps Upright Detector Inverted Detector Figure 4 26 Mount the detector l Position the right keyhole on the rear of the detector over the head of the right screw A Figure 4 27 A A Upright Detector Inverted Detector Figure 4 27 Position detector over screw l Sli...

Page 37: ...head of screw B Push the detector to the wall Figure 4 29 B B Upright Detector Inverted Detector Figure 4 29 Position detector on the second screw l Rotate the detector anticlockwise or clockwise for an inverted detector to lock the detector on to the screw Figure 4 30 Upright Detector Inverted Detector Figure 4 30 Rotate the detector 12 Insert an M4 screw at the small end of the detector s bottom...

Page 38: ...VESDA E VES A00 P Product Guide 32 www xtralis com Upright Detector Inverted Detector Figure 4 31 Locking screw 13 Tighten the top and bottom screws 14 Insert the pipes and electrical conduit ...

Page 39: ... is not UL tested Caution Electrostatic discharge ESD precautions need to be taken prior to removing the fascia from the detector in order to prevent damage to sensitive electronic components within the VES A00 P Attention Les precausions contre le decharge electrostatique dois etre respecter avant d ouvrir le panneau du detecteur afin de prevenir au dommage des composants electroniques a l interi...

Page 40: ...Alert I 5 Action J 7 Fire 2 K 8 First Alarm Sector 1 L 9 First Alarm Sector 2 M 10 First Alarm Sector 3 N 11 First Alarm Sector 4 O 12 Scanning P 6 Fire 1 Comms R Ethernet S USB GPI T Monitored GPI U Unmonitored GPI Ground V Jumper for ground fault monitoring Q Chassis Ground Terminal Figure 4 33 Socket Locations 4 3 3 Power Source There are two sets of power terminals on the main board Figure 4 3...

Page 41: ...fer to Codes and Standards Information for Air Sampling Smoke Detection on page iii 4 3 4 Communication Ports The front door must be opened in order to access the communication ports Refer to Section 7 2 for information on opening the front door and Figure 4 33 for the physical location of the ports Note For all connection methods the detector also provides a gateway to all the other devices on th...

Page 42: ... detector to be able to detect ground faults on the VESDAnet wiring the Ground Reference Terminal Figure 4 33 must be connected to the local ground A A B Shield Module 1 Module 2 Module 3 Module 5 Module 4 Shield B A A B Shield Shield B A A B Shield Shield B A A B Shield Shield B A A B Shield Shield B Figure 4 35 Example closed loop VESDAnet network The VESDA E VES A00 P detector is shipped with t...

Page 43: ...lay Operation URGENT FAULT Relay Fire 1 Relay No Fault Energized Fault or unpowered state No Fire De energized Fire Relay Assignments and Behaviour l Relays 1 2 4 5 7 8 9 10 11 12 are fully configurable l Relays 3 and 6 are fixed to Urgent Fault and Fire 1 respectively These relays may be assigned additional conditions l Relays 3 and 6 are changeover relays SPDT 1 Form C All the other relays are s...

Page 44: ...ector Fully configurable 12 Scanning No Energizes when the detector is scanning the inlet ports for smoke Fully configurable Table 4 2 Default Relay Assignments continued 4 3 7 Unmonitored General Purpose Input GPI The Unmonitored GPI is a programmable input which can be configured to initiate a number of different actions including by default a Remote Reset function Refer to Section 5 5 11 on pag...

Page 45: ...third party Input Output Loop module 3 inputs 1 output Note These are example drawings Refer to the appropriate product manual for the exact wiring details of the third party equipment Normally Closed NC Normally Open NO Normally Open NO Normally Closed NC Normally Open NO Fire Input EOL Normal Short Fire Open Wiring Fault EOL Normal Short Fire Fault Input EOL Normal EOL EOL EOL NC NO Monitored GP...

Page 46: ...tion codes and standards The size of the battery is determined by l local codes and standards l the total power required by the system l back up time required l allowance for reduction in capacity with age l expected temperature variations Note It is recommended that batteries be inspected and changed as per manufacturer s specifications or as per local codes and standards To facilitate the calcul...

Page 47: ...inals and that the polarity is correct On power up l The Power LED illuminates and the detector runs a series of self diagnostic tests l If there is a fault the Fault LED illuminates To identify the fault check the Active Event List for the detector using Xtralis VSC l The aspirator starts up and air may be felt flowing out of the exhaust port It is normal for the detector to display airflow fault...

Page 48: ...urther information The sampling air pipes are firmly connected to the air inlet ports Ensure that the pipes are NOT glued The power supply wiring has been connected to the detector If required the end of line resistor for the monitored GPI has been connected Refer to Section 4 3 11 on page 40 for further information The alarm and fault relay output terminals of the detector have been connected to ...

Page 49: ...lling the VES A00 P detector before it is commissioned for use To perform the preliminary system check l Power up the detector by connecting the power supply to the Power In terminal l Check that the display is functioning l Check that the aspirator is functioning by determining whether air is being expelled from the exhaust port ...

Page 50: ...VESDA E VES A00 P Product Guide 44 www xtralis com This page is intentionally left blank ...

Page 51: ...n l configure the respective parameters in the detector including the authentication password l create a connection profile for Ethernet or WiFi as required l connect to the detector USB is used for initial configuration however it must not be used for permanent connection Permanent connection for secondary monitoring must only be done with Ethernet or WiFi For example the installer would connect ...

Page 52: ...e 5 1 Connection Manager 2 Select Add The Add Connection dialog is displayed Figure 5 2 Figure 5 2 Add Connection 3 Select the VESDAnet connection option then select Next Adding a USB Connection 1 Select USB then select Next Figure 5 3 Figure 5 3 Select USB ...

Page 53: ...k the checkbox next to Remember Password and then enter the password that has been configured in the detector configuration General Options for Ethernet and WiFi connection See section 5 5 1 Figure 5 6 Warning If the Remember Password option is selected the user will not be required to enter the password when a connection is requested Users should be aware that saving the password in this manner m...

Page 54: ...VES A00 P Product Guide 48 www xtralis com Figure 5 6 Enter IP Address 3 Enter a unique name for the Connection or accept the pre generated name then select Finish Figure 5 7 Figure 5 7 Enter a Connection Name ...

Page 55: ...tor and the PC installed with Xtralis VSC can be made using a router or switch Figure 5 9 or directly between the two devices Complex networks are beyond the scope of this document For a successful connection Ethernet connectivity must be enabled within the detector the detector must have an IP address and an authentication password must be set Configuration procedures for these requirements are d...

Page 56: ... this document Figure 5 10 Connecting to a detector via WiFi using a router Enabling WiFi Connection The WiFi connection method only needs be configured once and then edited if there is a change to any of the relevant building network connection parameters 1 Connect to the detector using USB following the procedure described in Section 5 2 1 2 In the WiFi tab for the detector l For dynamic IP addr...

Page 57: ... detectors on the VESDAnet with WiFi disabled Figure 5 11 Connection to a detector via another detector on VESDAnet using a WiFi connection Alternatively it is possible to connect using a High Level Interface HLI connected between the PC or Laptop with Xtralis VSC and the VESDAnet Socket in one of the devices on the VESDAnet Notes l The VES A00 P detector acts as a gateway on VESDAnet and allows a...

Page 58: ... VES A00 P detector via Xtralis VSC user functionality is initially limited For additional privileges the user must log in to the detector using an 4 digit numeric PIN code In Xtralis VSC select Logon from the Connection menu and enter the PIN User Level Access Level Functional Authorization USR Low This is the USER or the OPERATOR level The user can view the event log and change the date and time...

Page 59: ...y mode End Standby The End Standby command is available when the detector is in Standby mode The End Standby command causes the detector to exit Standby mode Reset The Reset command unlatches all latched alarms and faults and returns relays to their normal state Clears the Xtralis VSC active event list Start Normalize Air Flow Starts the air flow normalization process for the selected detector The...

Page 60: ...low To cancel AutoLearn Smoke and Flow functions using the internal AutoConfig button press and hold the button for 5 seconds The LED will turn off Start AutoLearn Smoke Starts the AutoLearn Smoke process for the detector The detector monitors the environment and determines appropriate smoke thresholds The user is prompted to enter the monitoring period When the AutoLearn has finished the smoke th...

Page 61: ...detector will behave as if real smoke has been detected Alarm relays will energize unless the detector is disabled Start Air Flow Fault Test Tests the air flow sensing system by shutting down the aspirator Start Relay Test Tests the available relays by activating and deactivating as required Start LED Test Tests each LED by cycling through all LEDs on the detector display panel Return to Factory D...

Page 62: ...ame of the VESDAnet network The user can leave this blank if desired l Location A description of the physical location of the detector This name will appear on Xtralis VSC and on the LCD display of the A10 model detector l Serial Number The serial number of the device This is factory set and cannot be changed l VESDA Zone The unique zone number used to link this detector and remote display relay d...

Page 63: ...k data from this device The non preferred port is used if for some reason transmissions on the preferred port fail For best performance in large networks this setting should be randomly distributed between connected devices l Loop Open Ended on This Device This should be checked if the network has been wired so either VESDAnet port A or VESDAnet B is not connected on this detector Xtralis recommen...

Page 64: ... IP address Subnet Mask and Default Gateway fields are disabled Once the IP address has been successfully obtained by the detector it is displayed on the detector detail status screen Static IP Address Configuration l IP Address IPV4 static address This address must be used when creating a connection profile for the detector in Xtralis VSC l The default IP address is 192 168 0 200 This allows dire...

Page 65: ...isting WiFi network l WiFi Enabled Controls whether detector attempts to use WiFi and connect to an access point l Access Point SSID Set by installer to suit building access point l Security mode WPA2 mode only l WPA Key Use button to enter WPA2 key required to join building access point WiFi IP Configuration Parameters The following parameters allow setting of a dynamic or static IP address for t...

Page 66: ...imeouts Figure 5 16 Security Options l Maximum number of WiFi Ethernet connections The number of connections which can be running at any time WiFi and considered Ethernet together l USB Connection Idle Timeout minutes The USB connection will be dropped after no activity from the user on Xtralis VSC for this period of time l Ethernet WiFi connection idle timeout hours Ethernet and WiFi connections ...

Page 67: ...hrough 4 The settings for day time alarm thresholds for each sector 1 through 4 l Alarm Level Night Sector 1 through 4 The settings for night time alarm thresholds for each sector 1 through 4 l Set all to Sector 1 Press this button to set all thresholds to the thresholds set for Sector 1 l Scanning Sector Scan Time The duration for which the detector examines the air for each sector when scanning ...

Page 68: ...If the installation site flow conditions vary significantly it is recommended that the Major High and Major Low parameters are set closer to their limits l Major High The level of air flow considered to be so far above normal as to require urgent attention l Minor High The level of air flow considered to be above normal but not urgent l Minor Low The level of air flow considered to be below normal...

Page 69: ...option page allows you to define the time period after which a filter fault will be generated Figure 5 19 Filter Options Service Interval days The time period after a new filter is installed at which non urgent fault Filter smoke dust limit nearly exceeded Fault 767 will be generated ...

Page 70: ...Sector Names page allows the user to set the names of the sectors being monitored Figure 5 20 Filter Options Sector Name Sector Number 1 through 4 A description of the sector being monitored This name will appear on Xtralis VSC and on the LCD display of the A10 model detector ...

Page 71: ... of the VES A00 P detector monitoring the protected area is limited to 50 of the Fire 1 alarm threshold of the VES A00 P A single reference detector can be used by multiple VESDA detectors within the protected area The percentage of reference smoke level subtracted can be set differently for each detector monitoring the protected area This is set using the dilution factor parameter There may be a ...

Page 72: ...se Input Options The configuration options are as follows l GPI function Unmonitored and GPI function Monitored Refer to Table 5 3 below for a description of the individual selections l Button Lockout If the checkbox is ticked the Reset Disable and Acknowledge functions can t be executed using the front panel button Function State Change External Reset Unmonitored GPI The detector resets on a 0 VD...

Page 73: ...nitored GPI l The detector is held in Standby mode see Section 7 1 while 5 VDC l The detector exits Standby mode at a 5 VDC to 0 VDC falling edge Monitored GPI l The detector is held Standby mode see Section 7 1 while contact is closed l The detector exits Standby mode when the contact opens Note No alarms can be generated while the detector is in standby mode 0V 5V Standby Open Closed Enabled Sta...

Page 74: ...closure or opening of the contact and l The detector is held disabled while contact is closed l The detector is enabled when the contact opens 0V 5V Reset and enabled Disabled Reset Open Closed Disabled Reset Reset and enabled Inverted Reset Unmonitored GPI l The detector resets on a 5 VDC to 0 VDC falling edge Monitored GPI l The detector resets on the opening of the contact 0V 5V Reset Open Clos...

Page 75: ... In addition each relay can be configured Normally Energized or Normally De Energized Figure 5 23 Relay Options Relay Assignments Select the conditions you want to assign to each relay by checking the checkbox es under the relay The following checkboxes cannot be changed l Relay 6 always reports Fire 1 l Relay 3 always reports Urgent Fault and is always Normally Energised You can assign more than ...

Page 76: ...ve is removed from the relay coil when the condition occurs The default mode of the relays is listed in Table 4 2 Latching If the cause of a condition is removed for example smoke decreases below the threshold and latching is enabled the detector remembers the condition and holds the corresponding relays and displays in the active state as though the cause of the condition were still active Latchi...

Page 77: ... No Automatically Obtain IP Address Unchecked Unchecked Checked No IP Address 3 192 168 0 200 n a n a No Subnet mask 3 255 255 255 0 n a n a No Default Gateway Blank n a n a No WiFi WiFi Enabled Unchecked Unchecked Checked No WiFi Configuration No l Access Point SSID Blank n a n a No l Security Mode WPA2 WPA2 WPA2 No l Security Key 4 None n a n a No IP Address Configuration l Automatically Obtain ...

Page 78: ...e Change Logging 0 005 obs m 0 0016 obs ft 0 0001 obs m 0 000031 obs ft 0 2 obs m 0 0063 ofs ft Yes Significant Smoke Change VESDAnet 0 005 obs m 0 0016 obs ft 0 0001 obs m 0 000031 obs ft 0 2 obs m 0 0063 ofs ft Yes Scanning Sector Scan Time 8 seconds 8 seconds 15 seconds Yes Scanning Scan Delay 3 0 10 Yes Work Days Monday through Friday n a n a Yes Day Night Changeover Time l Enabled Unchecked U...

Page 79: ...tion Factor 100 1 100 Yes General Purpose Inputs GPI Function Unmonitored Reset n a n a Yes GPI Function Monitored Mains OK n a n a Yes Button Lockout Unchecked Unchecked Checked Yes Relays Assignment of Relays to conditions See Table 4 2 n a n a Yes Normally Energized See Table 4 2 n a n a Yes Latching Checked Unchecked Checked Yes Beep Unchecked Unchecked Checked Yes AutoLearn Smoke and Flow Com...

Page 80: ...VESDA E VES A00 P Product Guide 74 www xtralis com This page is intentionally left blank ...

Page 81: ...faults during this time 3 Set the Pipes in Use value in the Airflow configuration options 4 Set the aspirator setting to the value used when designing the system in ASPIRE to achieve the required transport time 5 Normalize the airflow This takes approximately 3 minutes after which the pipe flow rates should be close to 100 6 Reset the detector after normalization It should now be running without f...

Page 82: ...normal environmental background variations During the learning cycle if an alarm condition occurs AutoLearn will not complete its cycle In this situation the user must restart the AutoLearn process If AutoLearn is halted the alarm thresholds will be left at the previous settings Conditions experienced during learning are assumed to be representative of normal operating conditions The AutoLearn Smo...

Page 83: ...e flow thresholds will be left at the previous settings Conditions experienced during learning are assumed to be representative of normal operating conditions The AutoLearn Flow learning times can be set between 15 minutes and 16 days with the default being set to 14 days 6 3 Commissioning Smoke Test It is recommended that a smoke test be carried out to verify the integrity of the pipe network to ...

Page 84: ...VESDA E VES A00 P Product Guide 78 www xtralis com This page is intentionally left blank ...

Page 85: ...ing authority l Ensure that any ancillary devices dependent on the detector are isolated before work commences Attention Pendant que le detecteur ou la zone est desactivee aucun feu d indication va etre emis par le detecteur Avant tout entretien ou tester l Informer les autorité de supervision appropriée l S assurer que tout les appareils auxiliaires dépendants sur le détecteur sont isolés avant d...

Page 86: ...uide 80 www xtralis com 7 2 Open the Door Several maintenance functions require that front door be opened Open the Front Door 1 Open the door by inserting a thin screwdriver into hole B and pushing firmly Figure 7 1 Open the door ...

Page 87: ... high levels of contamination Remove the Filter Note that it is not necessary to turn off the 24V DC power to the detector when removing and replacing the filter The detector will turn off the aspirator when it detects that the filter has been removed and a fault will be signaled 1 Open the front door Ensure that the area around the filter is free of lint and dust before removing the filter Refer ...

Page 88: ...hich allow it to be tilted on the chamber manifold Figure 7 3 Tilt Filter towards the left hand side of the detector 4 Lift the filter out of the detector case Figure 7 4 Figure 7 4 Remove Filter Reinstall the Filter Note Ensure that the new filter is free of lint and dust 1 Tilt the filter towards the left and position its hinge pins in their recess Figure 7 5 ...

Page 89: ...ww xtralis com 83 Figure 7 5 Engage hinge pins 3 Tilt the filter to the right 4 Firmly press as shown in Figure 7 6 until the filter makes a distinct clicking sound and no additional movement is possible Figure 7 6 Reinstall the Filter ...

Page 90: ...moving the fascia from the detector A wrist strap must be connected to the case of the detector Figure 7 7 Attention Les precausions contre le decharge electrostatique dois etre respecter avant d ouvrir le panneau du detecteur Un bracelet doit être raccordé au panneau du détecteur Figure 7 7 Figure 7 7 Wrist Strap application Remove the Fascia 1 Turn off the 24V DC power to the detector 2 Remove t...

Page 91: ...VESDA E VES A00 P Product Guide www xtralis com 85 Figure 7 8 Fascia removal remove screws 3 Remove the fascia and allow it to hang by the two tether straps Figure 7 9 Fascia hanging on two tethers ...

Page 92: ... clear of dirt and debris prior to replacement Care must be taken during aspirator replacement The aspirator must be correctly seated it is essential to ensure that the gaskets are not damaged or dislodged from the underside of the aspirator Remove the Aspirator 1 Turn off the 24V DC power to the detector 2 Open the front door and remove the front fascia Refer to Sections 7 2 and 7 4 for further i...

Page 93: ...VESDA E VES A00 P Product Guide www xtralis com 87 Figure 7 12 Remove aspirator from the detector Reinstall the replacement Aspirator To replace the aspirator follow the removal procedure in reverse ...

Page 94: ...7 7 To replace the Smoke Detection Chamber perform the following steps 1 Open the front door and remove the front fascia Refer to Sections 7 2 and 7 4 for further information 2 Remove the Sampling Module as described in Section 7 7 on page 93 3 Remove Smoke Detection Chamber as described below 4 Install the new Smoke Detection Chamber as described below 5 Reinstall the Sampling Module as described...

Page 95: ...VESDA E VES A00 P Product Guide www xtralis com 89 Figure 7 13 Undo Chamber retaining screws 4 Disconnect the chamber loom from the connector labeled J3 Figure 7 14 ...

Page 96: ...VESDA E VES A00 P Product Guide 90 www xtralis com Figure 7 14 Disconnect Chamber Loom 5 Remove the chamber from the detector base Figure 7 15 Figure 7 15 Remove the Chamber from the detector base ...

Page 97: ... 16 Position the indicated loom sections beside the air flow sensing module not on top of it This will ensure that when installing the chamber the looms are not caught between the chamber and the air flow sensing module Figure 7 16 Position the gray loom 2 Position the chamber looms A and B as shown in Figure 7 17 A B Figure 7 17 Position the Chamber looms ...

Page 98: ...n the position shown so that the looms are not caught between the chamber and other parts of the detector Figure 7 18 Install the Chamber 4 Secure the four screws which hold the chamber to the detector base Figure 7 13 5 Reconnect the loom to J3 Figure 7 14 6 Reinstall the Filter Refer to Section 7 3 on page 81 for further information ...

Page 99: ...rea around the Sampling Module is clear of dirt and debris prior to replacement Care must be taken during Sampling Module replacement The Sampling Module must be correctly seated in order for a correct seal to be established between the Sampling Module and the rest of the detector It is essential to ensure that the rubber seal on the underside of the Sampling Module is correctly in place Removing ...

Page 100: ... P Product Guide 94 www xtralis com 4 Press on the lever on the connector to release the catch Figure 7 20 Figure 7 20 Release the Sampling Module cable 5 Undo the three screws holding the Sampling Module Figure 7 21 ...

Page 101: ...VESDA E VES A00 P Product Guide www xtralis com 95 Figure 7 21 Undo Sampling Module screws ...

Page 102: ...Sampling Module Figure 7 22 Figure 7 22 Remove Sampling Module Installing a replacement Sampling Module 1 Firmly press the Sampling Module into the detector in the direction of the arrow shown so that the rubber seal on the Sampling Module is seated on the pipes in the detector Figure 7 23 You will feel the module slide onto the pipes ...

Page 103: ...VESDA E VES A00 P Product Guide www xtralis com 97 Figure 7 23 Reinstall Sampling Module 2 Tighten the three screws and re connect the Sampling Module cable Figure 7 19 ...

Page 104: ...e Detection Chamber as described in Section 7 6 on page 88 6 Remove Ultrasonics Flow Sensing and Scanning Module as described below 7 Install the new Ultrasonics Flow Sensing and Scanning Module as described below 8 Reinstall the Smoke Detection Chamber as described in Section 7 6 on page 88 9 Reinstall the Sampling Module as described in Section 7 7 on page 93 10 Reinstall the Aspirator as descri...

Page 105: ...move the Ultrasonics Flow Sensing and Scanning Module Installing the replacement Ultrasonics Flow Sensing and Scanning Module 1 Re install the Ultrasonics Flow Sensing and Scanning Module into the detector base ensuring that the looms are not trapped under the module 2 Secure the three screws that hold the Ultrasonics Flow Sensing and Scanning Module to the detector base 3 Reconnect the main board...

Page 106: ...VESDA E VES A00 P Product Guide 100 www xtralis com ...

Page 107: ...ble 7 2 Spare Parts Part No Description VSP 955 VESDA E VES A00 P Scanner Manifold VSP 960 VESDA E Mounting Bracket VSP 961 VESDA E Exhaust Adaptor US VSP 962 VESDA E Filter VSP 962 20 VESDA E Filter 20 Pieces VSP 963 VESDA E Aspirator VSP 964 03 VESDA E Smoke Detection Chamber VSP 965 VESDA E Sampling Module VSP 968 VESDA E VES A00 P Front Cover Plastic LEDs VSP 969 S VESDA E VES A10 P Front Cove...

Page 108: ...VESDA E VES A00 P Product Guide 102 www xtralis com This page is intentionally left blank ...

Page 109: ...instances the fault relays signal a fault condition to the FACP or the BMS Use the Xtralis VSC software to further investigate the fault 8 2 Troubleshooting with Xtralis VSC The details of fault conditions are written to the detector s event log The event log can be retrieved using Xtralis VSC and the date time fault number and description of any faults can be viewed The Xtralis VSC software also ...

Page 110: ...VESDA E VES A00 P Product Guide 104 www xtralis com This page is intentionally left blank ...

Page 111: ...w l WPA 2 encryption must be used whenever Wi Fi is enabled l Restrict access to HLI devices to authorized personnel only l Passwords must be chosen in line with the guidelines in the detector user guide and provided to trusted users only l Default PIN codes must be changed as part of the initial configuration System Maintenance Requirements l Do NOT use the USB port for long term monitoring or al...

Page 112: ...VESDA E VES A00 P Product Guide 106 www xtralis com This page is intentionally left blank ...

Page 113: ...ire panel using the Xtralis VSC Relay Test command Turn each relay on off individually See below Relay 1 Tested Default assignment Disable Relay 2 Tested Default assignment Minor Fault Relay 3 Tested Default assignment Urgent Fault Relay 4 Tested Default assignment Alert Relay 5 Tested Default assignment Action Relay 6 Tested Default assignment Fire 1 Relay 7 Tested Default assignment Fire 2 Relay...

Page 114: ... Sector 4 Fire 2 Fire 1 Action Alert First Alarm Urgent Fault relay connection to fire panel tested using the Xtralis VSC Urgent Fault Test command Minor Fault relay connection to fire panel tested using the Xtralis VSC Minor Fault Test command Smoke Test done Transport time tested Scanning relay connection to Fire Panel verified Disable Standby Relay connection to Fire Panel Verified ...

Page 115: ...ault Relay 3 Tested Default assignment Urgent Fault Relay 4 Tested Default assignment Alert Relay 5 Tested Default assignment Action Relay 6 Tested Default assignment Fire 1 Relay 7 Tested Default assignment Fire 2 Relay 8 Tested Default assignment Sector 1 Relay 9 Tested Default assignment Sector 2 Relay 10 Tested Default assignment Sector 3 Relay 11 Tested Default assignment Sector 4 Relay 12 Te...

Page 116: ...ion to Fire Panel verified using the Xtralis VSC Fault Test command for the detector Disable Standby Relay connection to Fire Panel Verified Scanning relay connection to Fire Panel verified Client Representative Name Test witnessed by Date Hand Over Documents Copy of this form ASPIRE Installation Data Pack ASPIRE Bill of Materials Configuration printout from Xtralis VSC for each detector Configura...

Page 117: ...mand on the File menu A 2 ASPIRE Data Print the ASPIRE Installation Data Pack IDP in order to record the ASPIRE modeling results for the system A 3 Smoke Test Table A 2 Smoke Test commissioning form Test Results Test Method Type of Smoke Test Date A 4 Air Sampling Test Results Table A 3 Air Sampling Test results commissioning form Pipe 1 Pipe 2 Pipe 3 Pipe 4 Transport Time from End Cap Hole Test 1...

Page 118: ...VESDA E VES A00 P Product Guide 112 www xtralis com This page is intentionally left blank ...

Page 119: ... for example alarms troubles user commands which is stored in the detector F Fault An urgent fault is a condition where the system requires urgent attention as it may be unable to detect an alarm condition A minor fault is a condition where the system requires attention or maintenance but is still able to detect an alarm condition Fire Alarm Control Panel FACP A central monitoring and control syst...

Page 120: ...protected area Relay A device on a detector that has an electrical contact which can be configured to close when a condition occurs such as fire alarm or a fault in the detector This is the primary method used to signal alarms and faults S Sampling Network The pipe network constructed to allow the VESDA E detector to draw air for sampling Sensitivity Sensitivity refers to sensitivity to smoke A hi...

Page 121: ...oLearn smoke 54 disable 53 enable 53 normalize air flow 53 rebuild zone list 55 reset 53 return to factory defaults 55 set system date and time 55 standby 53 start air flow fault test 55 start alarm test 55 start AutoLearn flow 54 start AutoLearn smoke 54 start lamp test 55 start major fault test 55 start minor fault test 55 start relay test 55 commissioning 75 107 113 smoke test 77 connection 7 4...

Page 122: ...oltage 38 66 reset isolate 66 standby mode 66 unmonitored 3 34 38 39 66 113 use night time threshold 68 H HLI 8 51 113 I isolate 34 37 68 L LED 3 5 7 41 66 79 103 M maintenance 10 check pipe flow 79 check pipe network 79 clean sampling point 79 filter inspection 79 flush pipe network 79 pipe integrity smoke test 79 power supply 79 mounting 9 27 29 42 bracket 17 location 18 locking mechanism 27 ori...

Page 123: ...ays 3 5 7 9 34 37 39 41 53 66 69 103 113 action 34 alert 34 fault 34 37 fire 34 37 isolate 34 options 69 remote display 8 56 103 reset 5 7 38 41 53 66 68 75 S sampling module 5 93 101 sensitivity 3 9 113 settings 71 default 71 significant smoke change 61 specifications 9 alarm range 9 dimensions 9 power 9 weight 9 standby 53 67 79 81 86 88 supply voltage 9 34 T temperature 9 40 thresholds 5 9 acti...

Page 124: ...VESDA E VES A00 P Product Guide 118 www xtralis com Z zone 55 56 79 113 ...

Reviews: