VESDA-E VES-A00-P Product Guide
www.xtralis.com
9
2.7
Specifications
Specification
Value
Supply Voltage
18 to 30 VDC (24 VDC Nominal)
Power Consumption @24 VDC
Power (Quiescent)
9.7 W
Setting 1
Setting 5
Setting 10
Power (In Alarm)
9.9 W
7.9 W
8.5 W
14.8 W
14.5 W
Aspirator
Peak current: 1.5A
Dimensions (WHD)
350 mm x 225 mm x 135 mm
(13.8 in x 8.9 in x 5.3 in)
Weight
4.3 kg (9.5 lb)
Operating Conditions
Please consult your Xtralis representative for
information on operation outside these parameters
or where sampled air is continually above 0.05%
obs/m (0.015% obs/ft) under normal operating
conditions.
l
Ambient: 0°C to 39°C (32°F to 102°F) *
l
Tested to (EN54-20): -10°C to 55°C (14°F to 131°F)
l
Sampled Air: -20°C to 60°C (-4°F to 140°F) **
l
Humidity: 5% to 95% RH, non-condensing
* Product UL listed for use from 0°C to 38°C (32°F to 100°F)
** Sampled Air temperature shall reach Ambient Detector
temperature upon entry into Detector. Refer to Xtralis Design
Guides & Application Notes for sampled air pre-conditioning.
Storage Conditions
(Non-operational)
l
Humidity:
Dry (<95%)
l
Temperature:
0° to 85°C
l
Must not be exposed to sunlight or other radiation sources
Sampling Pipe Network
l
Maximum length per pipe when using four straight
pipes:
l
Four pipe VES-A00-P: 70 m (230 ft)
l
Maximum total pipe length (with branches):
l
Four pipe VES-A00-P: 560 m (1,837 ft)
l
Pipe Modeling Design Tool:
ASPIRE
l
Minimum airflow per pipe:
15 l/m
Note:
Standards compliance of a particular pipe network
must be determined using ASPIRE.
Inlet Pipe Size
l
External Diameter:
25 mm or 1.05 in (3/4" IPS)
Exhaust Pipe Size
l
External Diameter:
25 mm or 1.05 in (3/4" IPS) via
adaptor
Relays
l
12 programmable relays
l
Contacts rated 2A @ 30 VDC (Resistive)
l
Programmable to latch or not latch alarm or fault states
IP Rating
IP 40
(not UL tested)
Mounting
Upright or inverted
Cable Access
4 x 26 mm (1 in) ports
Cable Termination
Screw terminal blocks (0.2-2.5 sq mm, 24-14 AWG)
Interfaces
l
USB (Type 2)
l
Ethernet (RJ45)
l
WiFi, 802.11 b/g/n
Dynamic Range
0.0002%/m to 32%/m (10%/ft to 0.00006%/ft)
Table 2-2: VES-A00-P Detector Specifications
Summary of Contents for VESDA-E VES-A00-P
Page 2: ......
Page 10: ...VESDA E VES A00 P Product Guide 4 www xtralis com This page is intentionally left blank ...
Page 20: ...VESDA E VES A00 P Product Guide 14 www xtralis com This page is intentionally left blank ...
Page 50: ...VESDA E VES A00 P Product Guide 44 www xtralis com This page is intentionally left blank ...
Page 80: ...VESDA E VES A00 P Product Guide 74 www xtralis com This page is intentionally left blank ...
Page 84: ...VESDA E VES A00 P Product Guide 78 www xtralis com This page is intentionally left blank ...
Page 101: ...VESDA E VES A00 P Product Guide www xtralis com 95 Figure 7 21 Undo Sampling Module screws ...
Page 106: ...VESDA E VES A00 P Product Guide 100 www xtralis com ...
Page 108: ...VESDA E VES A00 P Product Guide 102 www xtralis com This page is intentionally left blank ...
Page 110: ...VESDA E VES A00 P Product Guide 104 www xtralis com This page is intentionally left blank ...
Page 112: ...VESDA E VES A00 P Product Guide 106 www xtralis com This page is intentionally left blank ...
Page 118: ...VESDA E VES A00 P Product Guide 112 www xtralis com This page is intentionally left blank ...
Page 124: ...VESDA E VES A00 P Product Guide 118 www xtralis com Z zone 55 56 79 113 ...