    EVHR Hybrid Ventilation Unit

Installation, Operation and Maintenance Manual

Six Monthly Checks

Spares & Repairs

Recommended Checks

Continued

For units prior to March 2019

,

 

the fans are mounted directly onto the fan bulkhead.

To remove the fans, ensure the unit is fully isolated and that any moving components have come
to a halt. Remove the side access panels. Separate the connecting fan plug and socket, using the
procedure as detailed on page 10. Carefully remove the double deflection grille from the bottom
of the unit retaining the fixings, and remove the  fixings holding the appropriate fan. Remove the
fan through the side access and replace as required. Again ensure all fixings are reinstated, that
the plug and socket are correctly assembled and that loose cables are safely stowed away from
all moving parts.

In order to keep the unit in good order the following maintenance routine is recommended:

The fan impeller should be cleaned every 6 months. Failure to clean the fan on a regular basis could
result in loss of fan performance, or cause it to fall out of balance. If a fan is stationary for long periods
in a humid atmosphere, it should be switched ON for minimum of two hours every month to remove
any moisture that may have condensed within the motor.
The fan motors are maintenance free due to the use of ball bearings with ‘life-long lubrication’.
At the end of the grease life it may be necessary to change the fan unit.
Failure to keep dampers clean could result in the damper becoming inoperative. Clean damper
blades and frames and lubricate with PTFE aerosol or equivalent.

For units with integrated heating, the heating coil should be inspected for debris, dust or dirt build
up. If found contaminated, foreign matter should be removed accordingly; superficial dust or debris
can be removed from the surface of the heat exchange by gently brushing. Loosened debris can then
be vacuumed from the surface of the coil.

When enquiring after or ordering spares contact VES Spares Department, quoting the sales order (SO)
number and unit type as found on the unit nameplate.

Tel: 023 8046 1150 • Fax: 023 8026 1204

At the end of their useful life the packaging and product should be disposed of via a suitable
recycling centre. Do not dispose of with normal household waste. Do not burn.

PLEASE ENSURE THAT THIS DOCUMENT IS PASSED ON TO THE END USER

We reserve the right to alter the specifcation without notice ©VES Andover Ltd. 2019.
No part of this publication may be photocopied or otherwise reproduced without the prior permission in writing
from VES Andover Ltd.

Maintenance

6

WEEE Directive

Fan Fixings

Supply Grille
(removed)

Supply Fan assembly
removal/installation

Fig. 

25

Summary of Contents for Ecovent EVHR

Page 1: ...lectric current and high voltages Indicates hazards that require safety advice for personnel or potential unit property damage Indicates important information page Introduction 1 Nomenclature 2 Receip...

Page 2: ...5 Fan Size 3 4 Sequential 6 Phase 1 230V 50Hz Single Phase 7 Main Heating Null No Heating W LPHW Coil E Electric Heater Battery 8 Main Filter Null No filter 9 Control Panel Section Null No Controls CP...

Page 3: ...fitted or steps taken to prevent this It is the installer s responsibility to ensure that access panels are not obstructed in any way Safe working access for maintenance must be provided in accordance...

Page 4: ...ontinued Ecovent EVHR units are designed to be mounted flush against the underside of the ceiling slab connected to a purpose made terminal or turret The connecting duct needs to be split so as to dif...

Page 5: ...46 1150 Fax 023 8026 1204 E mail vesltd ves co uk Web www ves co uk EVHR Hybrid Ventilation Unit Installation Operation and Maintenance Manual Continued Installation 4 Key installation components Fan...

Page 6: ...uded as part of the unit sealing only When moving assembled units ensure that ALL sections are fully supported Bracket Fixings Finishing Flange Moun ng Bracket Ecovent EVH units feature fresh air supp...

Page 7: ...pendently supported by structural trimmers in accordance with local building regulations in order to protect plant weight and support any service personnel The EVHR turret is designed to be mounted ho...

Page 8: ...W units are fitted with a coil temperature sensor as standard ensuring that boilers run continuously in low ambient temperatures can help to prevent this On Ecovent EVHR W units a Low Pressure Hot Wat...

Page 9: ...ng care with the supply sensor cable separate the sections If rotating the coil section 90 reposition the coil section joing bracket to the next face as shown in fig 12 This bracket repositioning is n...

Page 10: ...tions to match the required configurationas shown in fig 13 again take care with the sensor cable If at floor level this is eassiest to acheive by lifting and rotating the fan section Installation 4 C...

Page 11: ...ough the building installation device and a dedicated isolated power supply with overload protection to account for motor start up currents Do not connect any unit to an electrical supply voltage outs...

Page 12: ...Eastleigh Hampshire SO53 4NF Tel 023 8046 1150 Fax 023 8026 1204 E mail vesltd ves co uk Web www ves co uk EVHR Hybrid Ventilation Unit Installation Operation and Maintenance Manual Standard Wiring F...

Page 13: ...t Eastleigh Hampshire SO53 4NF Tel 023 8046 1150 Fax 023 8026 1204 E mail vesltd ves co uk Web www ves co uk EVHR Hybrid Ventilation Unit Installation Operation and Maintenance Manual Standard Wiring...

Page 14: ...Healthy indication will stop illuminating until the unit resumes normal operation The Open windows indication shall illuminate when the external temperature reaches a suitable level to encourage manu...

Page 15: ...as the wind and elements may cause moving parts to windmill In general this series of units require little maintenance In the unlikely event of component failure spares are available from stock at VES...

Page 16: ...using 4No M6 fixings To remove the fans ensure the unit is fully isolated and that any moving components have come to a halt Remove both side access panels Separate the connecting fan plug and socket...

Page 17: ...be switched ON for minimum of two hours every month to remove any moisture that may have condensed within the motor The fan motors are maintenance free due to the use of ball bearings with life long...

Reviews: