Verve VTST-9 User Manual Download Page 2

Configuration Parameters:  Access Code 43

Some parameters will change depending on whether the
equipment type is a fan coil or a heat pump.

Explanation of Codes:

Equipment Type (E9P):  

Selects the type of equipment

FC - Default, fan coil

tHp - Trane heat pump, type O reverse valve
tAc - Trane AC with electric heat

 

FHp - Friedrich heat pump, type B reverse valve

 

FAc - Friedrich AC with electric heat

 

gHp - GE heat pump, type B reverse valve

 

gAc - GE AC with electric heat

 

AHp - Amana heat pump, type B reverse valve

 

AAc - Amana AC with electric heat

Fan Speed and Operation (FOp):

Three speed fan only available for fan coil equipment

3U - Default fan coil, three speed user selectable fan

 

3C - three speed constant fan

 

3A - three speed auto fan

 

2U - Default heat pump, two speed user selectable fan
2C - two speed constant fan

 

2A - two speed auto fan

 

1U - single speed user selectable fan

 

1C - single speed constant fan

 

1A - single speed auto fan

Compressor Protection (FCp):

Selects the compressor protection and high or low speed fan in
heating

 

NP - Default fan coil, no compressor protection and high

 

fan is allowed in heating

CP - Default heat pump, compressor protection and high

 

fan is allowed in heating

 

nP - no compressor protection and only low fan is allowed 

 

in heating

 

cP - compressor protection and only low fan is allowed in 

 

heating

Continuous Fan Operation (CFL):

Selects continuous fan operation

dis - Default, normal fan operation

 

Ena - continuous low fan in auto or economy modes

Reverse Valve Type (typ):

Selects the valve type

O type - Default, energizes in calls for cooling
b type - energizes in calls for heating

Heat Pump or AC (Pt):

HP - Default, 2 stage heat, single stage cool

Y = compressor, W = 2nd stage heat

 

AC - AC and electric heat

Y = cool, W = heat

Sending a Teach-in Telegram:
Press 

the up or down arrow button to select Teach-in (tEa) mode.

Pressing

 the fan button will trigger the thermostat to send a

teach-in message.

To exit, 

Move

 the F/C switch to the opposite position.

EnOcean Connectable Devices:

Validate that the desired device has one of the EEP’s listed below.
Learn and clear modes will time out 30 seconds after the last
device has been added or deleted.

RPS Telegrams Accepted:

EEP: 05-10-00 – Window handle
EEP: 05-04-01 – Keycard activated switch
EEP: 05-02-02 – PTM 210 or equivalent

F6-10-00: Window Handle
F6-04-01: Key Card Activated Switch
F6-02-02: PTM200 / PTM 210 or equivalent

1BS Telegrams Accepted:

EEP 06-00-01 – Single input contact
D5-00-01: Single Input Contact

4BS Telegrams Accepted:

A5-02-04: Temperature Sensor Range -10°C to +30°C
A5-02-05: Temperature Sensor Range 0°C to +40°C
A5-02-06: Temperature Sensor Range +10°C to +50°C
A5-02-07: Temperature Sensor Range +20°C to +60°C
A5-02-15: Temperature Sensor Range -10°C to +70°C
A5-04-01: Range 0°C to +40°C and 0% to 100%
A5-07-01: Occupancy
A5-07-02: Occupancy Sensor
A7-07-03: Occupancy Sensor
A5-08-01: Range 0lx to 510lx, 0°C to +51°C and Occupancy
A5-08-02: Range 0lx to 1020lx, 0°C to +51°C and Occupancy
A5-08-03: Range 0lx to 1530lx, -30°C to +50°C and Occupancy
A5-30-01: Single Input Contact, Battery Monitor
A5-30-02: Single Input Contact
A5-38-08: Central Gateway

EEP: 07-02-04 – Temperature sensor, range -10°C to 30°C
EEP: 07-02-05 – Temperature sensor, range 0°C to 40°C
EEP: 07-02-06 – Temperature sensor, range 10°C to 50°C
EEP: 07-02-07 – Temperature sensor, range 20°C to 60°C
EEP: 07-02-15 – Temperature sensor, range -10°C to 70°C
EEP: 07-04-01 – Temperature and Humidity sensor, range 0°C to 40°C,
  0% to 100%
EEP: 07-07-01 – Occupancy sensor
EEP: 07-07-02 – Occupancy sensor
EEP: 07-07-03 – Occupancy sensor
EEP: 07-08-01 – Only occupancy sensor used
EEP: 07-08-02 – Only occupancy sensor used
EEP: 07-08-03 – Only occupancy sensor used
EEP: 07-30-01 – Digital input, single input contact, battery monitor
EEP: 07-30-02 – Digital input, single input contact
EEP: 07-38-08 – Central Gateway

NOTES:

All single input contacts (EEP: 06-00-01, 07-30-01, 07-30-02) and
window handle inputs (EEP: 05-10-00) will place the thermostat into
shutdown mode when any of the contacts are open (any door or
window is open).  Thermostat will resume normal mode when all
contacts are closed (all doors and windows are closed).

 