Vertiv
|
NetSure V200D50 DC Power Retrofit Installation & User Manual (UM486527803)
|
Rev. F
8
Figure 1:
Output Voltage vs. Output Current
Power Derating Based on Input Voltage: See
Figure 2:
Output Power vs. Input Voltage
Regulation (Rectifier Default):
a)
Voltage Regulation: ≤±1%
b)
Load Regulation: ≤±0.5%
c)
Line Regulation: ≤±0.1%
d)
Overshoot at Startup: ≤±1%
e)
Dynamic Response (at rated input and output voltage values):
Response time is ≤200
µ
s, and the overshoot is ≤5% for load changes at 50%-25%-50% and 50%-75%-
50%.