Install the Mounting Frame
The Retrofit Mounting Frame CANNOT be installed in the Power Bay unless all Rectifiers are first
removed from the Mounting Frame. Doing so will defeat the precharge circuit in the rectifiers and cause
arching and pitting on the DC power connector!
Checking the Power Bay’s Rectifier AC/Data Connector in Older Style Bays
Identifying Older Style Bays
1.
Older style bays have Rectifier AC/Data connectors that do not have springs as shown in
. In
bays that have Rectifier AC/Data connectors without springs, perform the following procedure.
Figure 6:
Identifying Older Style Bays
Rectifier
AC/Data
Connector
Spring
Newer Style Bays
Have the Springs,
Older Style Bays
Do Not Have Springs
Spring