![Vertiv NetSure R48-2000 User Manual Download Page 15](http://html1.mh-extra.com/html/vertiv/netsure-r48-2000/netsure-r48-2000_user-manual_1007949015.webp)
Vertiv
|
NetSure Rectifier Module User Manual (UM1R482000e / 11BU1360YY)
|
Rev. J
15
Table 7:
Typical Input Data (1R482000): 50 Hz input
Nominal
Input
Voltage
Percent
of Full
Load
Input
Current
(Amperes)
Input
VA
Input
Watts
Power
Factor %
Efficiency
%
Heat
Dissipation
BTU/Hr
208
0
0.26
53.8
28
52.00
--
95.54
25
2.55
529.2
526
99.40
89.55
187.56
50
4.95
1029.3
1029
99.97
91.65
293.16
75
7.40
1535.2
1535
99.99
91.54
442.94
100
10.00
2065.8
2065
99.96
90.80
648.59
110
10.72
2220.7
2220
99.97
90.36
730.03
120
10.76
2232.9
2232
99.96
89.75
780.85
240
0
0.29
65.9
27
41.00
--
92.13
25
2.22
531.1
525
98.86
89.86
181.62
50
4.29
1028.7
1027
99.83
91.88
284.42
75
6.37
1531.3
1531
99.98
91.85
425.70
100
8.57
2057.2
2057
99.99
91.20
617.94
110
9.24
2215.2
2215
99.99
90.90
688.09
120
9.28
2220.2
2220
99.99
90.32
733.07
NOTE!
System output is initially adjusted to 54.48 volts DC as measured at the system sense point at
50% of full load and nominal input. “Percent of Full Load” refers to percent of 34.5 amperes.
Table 8:
Maximum Input Current (1R482000): 50 Hz input
Nominal
Input Voltage Input Voltage
Input Current
(Amperes)
208/240
176
12.33
NOTE!
At 100% of full load with output adjusted to 58 volts DC as measured at the shelf output
terminals.