NetSure Monitor Unit User Manual (UM1M832DNA)
|
Rev. C
157
TL1 Autonomous Message Sample
The DI1 alarm occurs.
When the alarm occurs, the monitor unit sends this autonomous message:
LorainLab 15-09-24 13:49:42
*C 8 REPT ALM EQPT
"PowerSystem:CR,Alarm,SA,09-24,13-49-41,,,0,0,0-MIN:\"DI1 Alarm\","
;
<
When the alarm clears, the monitor unit sends this autonomous message:
LorainLab 15-09-24 13:50:06
A 9 REPT ALM EQPT
"PowerSystem:CL,Alarm,SA,09-24,13-50-06,,,0,1,0-MIN:\"DI1 Alarm\","
;
<
Table of TL1 Commands Supported
for a list of all TL1 commands supported, with a short description of each command.
Table 10:
TL1 Commands Supported
TL1 Commands Supported
Description
ACTIVATE-USER
ACT-USER
Sets up a session with the system (i.e., logging into the
system).
CANCEL-USER
CANC-USER
Terminates a session with the system (i.e., logging off of the
system).
RETRIEVE-ALARM
RTRV-ALM-{EQPT|ALL}
Instructs the system to send the current state of its alarm
conditions associated with one or more equipment units,
facilities, etc. within the system.
RETRIEVE-EQUIPMENT
RTRV-EQPT
Instructs the system to send the current monitor unit
software version and the monitor unit software configuration
part number and revision.
RETRIEVE-HEADER
RTRV-HDR
Requests that the system reply with a "normal" response
indicating COMPLD.