![Vertiv NetSure ITS Series Installation And User Manual Download Page 20](http://html1.mh-extra.com/html/vertiv/netsure-its-series/netsure-its-series_installation-and-user-manual_1008117020.webp)
Vertiv™ NetSure™ ITS 12V DC Power Shelf Installation & User Manual
12
Connections to List 02 Module Mounting Assembly
Spec. No. 588706100 List 02 Module Mounting Assembly is configured for two (2) 208 VAC / 240 VAC, 50 Hz / 60 Hz, 3-phase AC
input feeds per module mounting assembly. One feeds 208 VAC / 240 VAC input voltage to six (6) modules plus the convenience AC
outlets on one side; the other 208 VAC / 240 VAC input voltage to three (3) modules plus the convenience AC outlets on one side.
If a cable was not ordered with the shelf, customer to install conduit or cord grips using the AC input access hole in the rear of the
shelf, and wire to the AC input terminal block located behind the rear access cover. See
. See System Application Guide
(SAG588706100) for recommended wire size and branch circuit protection device rating.
Figure 5-6:
AC Input Connections to a 588706100 List 02 Module Mounting Assembly (Hardwired)
AC Input Connections, 588706100 List 02, Hardwired
Nominal 208 VAC / 240 VAC, 50 Hz / 60 Hz, 3-Phase, 2 Feeds per Module Mounting Assembly
(1 Feed per 6 Module Positions, 1 Feed per 3 Module Positions)
AC Feed #2
(Positions #7 - #9)
208 VAC / 240 VAC,
50 Hz / 60 Hz, Three Phase
L1 - L2: Position #7
L2 - L3: Position #8
L1 - L3: Position #9
L1 - L3: Convenience Outlet #1
AC Feed #1
(Positions #1 - #6)
208 VAC / 240 VAC,
50 Hz / 60 Hz, Three Phase
L1 - L2: Position #1, #4
L2 - L3: Position #2, #5
L1 - L3: Position #3, #6
L1 - L2: Convenience Outlet #2
Rear (back panel removed for clarity only)
Front
Rectifier Module
Mounting Positions
#1 #2 #3 #4 #5 #6 #7 #8 #9
GND
FRAME GROUND CONNECTION
One M6 stud and hardware.
Torque: 5.7 Nm (50 in-lbs.)
L2 L3
L1
L2 L3
L1
AC INPUT
Wire Size Capacity: 16 to 2 AWG.
Torque: 2.5 to 4.5 Nm (22.1 to 39.8 in-lbs.)
Convenience
Outlet #1
Convenience