Vertiv™ NetSure™ External Distribution Box (EDB) Description and Installation Manual
Proprietary and Confidential © 2022 Vertiv Group Corp.
29
Figure 11.7 Typical Power System LVD Connections to Alarm BLOCK 2 (Vertiv™ NetSure™ 5100 DC Power System, Spec. No.
582137100 List 26, 582137100ZZ028 Shown. Others Similar.)
Vertiv™ NetSure™ 5100 DC Power System,
Spec. No. 582137100 List 26 (582137100ZZ028)
Shown. Others Similar.
Notes:
1. Factory installs links
on the factory wiring
side of terminal.
Factory Wiring Side
Customer Wiring Side
LVD+ LVD- LVD AUX
Contacts
CBA Alarm Signal to
DC Power System
Digital Input
LVD Coil
Block 1 and Block 2:
Wire Size Capacity:
20 AWG to 22 AWG.
Components removed in
illustration for clarity only.
Red Wire to LVD+
Black Wire to LVD-
White Wire to LVD
AUX Contacts
P/N 60031373
(30 Feet)
Strip the wire and crimp
P/N 140968 spade lug to
end of each wire.
Rear
Plug the two wire
harness connectors
labeled LVD1 together.