Vertiv
™
NetSure
™
802 and Vertiv
™
NetSure
™
8200 -48 VDC Power System
System Application Guide
Spec. No: 582140000
SAG582140000
Model Nos: 802
NLDB
, 802
NLEB
, 802
NL
-
B
,
Proprietary and Confidential © 2022 Vertiv Group Corp.
Revision BH, September 28, 2022
8200
NLDB
, 8200
NLEB
and 8200
NL
-
B
Page 56
Optional Bullet Nose-Type 10-Position GMT Fuse Module for List C
Features
♦
Installs in the optional
Fuse/Circuit Breaker Panel.
♦
Provides 10 GMT fuse positions.
(1/4A to 15A GMT Alarm-Type Fuses).
♦
Screw clamp type load and load return terminals provided.
♦
Includes ten dummy fuses equipped with safety fuse covers.
♦
Includes 35 A input fuse and associate alarm fuse.
Restrictions
30 A maximum capacity per block.
Terminal block wire size capacity: 24 to 14 AWG.
Requires five (5) bullet device mounting positions.
When used for power distribution, load should not exceed 80% of device rating, except
10 and 15 Amp fuses, for which load should not exceed 70% of device rating.
Ordering Notes
1)
Order optional Bullet Nose-Type 10-Position GMT Fuse Module (P/N 509128) as
required.
2)
Order GMT fuses as required per Table 6.
3)
See “
Replacement Alarm, Reference, and Control Fuses
” and Table 9 for ordering replacement input fuse and associated
alarm fuse.
Ampere Rating
Part Number
Fuse Color
18/100 GMT-A
248610301
---
1/4
248610200
VIOLET
1/2
248610300
RED
3/4
248610500
BROWN
1-1/3
248610700
WHITE
2
248610800
ORANGE
3
248610900
BLUE
5
248611000
GREEN
7-1/2
248611300
BLACK-WHITE
10
248611200
RED-WHITE
15
248611500
RED-BLUE
Replacement Safety
Fuse Cover
102774
---
Replacement
Dummy Fuse
248872600
---
Table 6
Bussmann GMT-Type Fuses
P/N 509128
GMT Fuse Module