NetSure Circuit Breaker Assembly (Section 5930)

 

|

 

Rev. C 

DESCRIPTION 

Part No. 520406 is a Circuit Breaker Assembly that accepts up to two (2) separately ordered GJ-type circuit 
breakers.  The assembly will accept a third circuit breaker if an accessory Circuit Breaker Mounting Kit is 
ordered and installed.  This Circuit Breaker Assembly is designed for wall mounting.  Furnished brackets permit 
mounting in either a 19” or 23” relay rack.  See 

Dimensions

 for mounting details.  See 

Table 1

 for a list of 

available circuit breakers. 

 

NOTE!  

Input Return and Load Return wiring is external to this assembly, and must be furnished by the 

customer. 

This panel is UL Listed as a DC Power Distribution Center for Communication Equipment.  In addition, this unit 
meets the requirements of CSA 22.2, No. 225 and is tested and Certified by UL ("c UL") as a Custom Built Power 
Distribution Center for Communications Equipment. 

 

ACCESSORIES 

GJ-Type Circuit Breakers 

Order circuit breakers from the following table per job requirements. 

Table 1:  

 

Ampere 

Rating 

Number of 

Mounting 

Positions 

Part Number 

 

Electrical/ 

Mechanical Trip

1

 

Part Number 

 

Electrical Trip

2

 

100 

256621700

 

256621300

 

125 

256621600

 

256621400

 

150 

256621800

 

256622400

 

175 

256621900

 

256622500

 

200 

256622200

 

256622600

 

225 

256622900

 

256622700

 

250 

256623500

 

256623400

 

Circuit Breaker Alarm Operation: 
1.  Provides an alarm during an electrical or manual trip condition. 
2.  Provides an alarm during an electrical trip condition only.

 

 

Circuit Breaker Mounting Kit 

Provides components needed to mount a third circuit breaker in the panel.  Order kit Part No. 520635. 

 

NOTE!  

Do not order for first two circuit breakers. 

 

Summary of Contents for NetSure 520406

Page 1: ...NetSure Circuit Breaker Assembly Installation Manual Section 5930 Revision C Specification Number 520406...

Page 2: ...rials to be used in performing procedures not specifically described in this document This document may contain confidential and or proprietary information of Vertiv Group Corporation and its receipt...

Page 3: ...BLE OF CONTENTS Admonishments Used in this Document 4 Important Safety Instructions 5 Safety Admonishments Definitions 5 General Safety 5 Description 7 Accessories 7 GJ Type Circuit Breakers 7 Circuit...

Page 4: ...d ANSI OSHA This admonition is not used for situations that pose a risk only to equipment data or service even if such use appears to be permitted in some of the applicable standards OSHA ALERT Alerts...

Page 5: ...ified technicians familiar with the hazards associated with this type of equipment These hazards may include shock energy and or burns To avoid these hazards a The tasks should be performed in the ord...

Page 6: ...Vertiv NetSure Circuit Breaker Assembly Section 5930 Rev C 6 This page is intentionally blank...

Page 7: ...n addition this unit meets the requirements of CSA 22 2 No 225 and is tested and Certified by UL c UL as a Custom Built Power Distribution Center for Communications Equipment ACCESSORIES GJ Type Circu...

Page 8: ...SEE DETAIL A FOR OPTIONAL CONDUIT PLATE FRONT VIEW 18 250 19 000 23 000 16 000 WALL MOUNTING HOLES IN REAR PANEL CUTAWAY VIEW 5 220 2 250 1 480 17 000 22 250 WIRING ACCESS OPENINGS SAME ON BOTTOM SEE...

Page 9: ...using supplied hardware Refer to Figure 2 for lug mounting details Lugs must be supplied by the installer Lug mounting hardware must be supplied by the installer except for factory furnished hardware...

Page 10: ...VertivCo com Vertiv Headquarters 1050 Dearborn Drive Columbus OH 43085 USA Section 5930 RC 12 17...

Reviews: