Vertiv
|
NetSure 502NGFB Installation Manual (Section 6009)
|
Rev. Z
68
4.
To Change a Parameter:
Press the UP or DOWN arrow keys to move the cursor up and down the list of parameters in the menu
screen (selects the parameter to change), then press ENT to change the selected parameter. The
parameter field highlights. Press the up or down arrow keys to change the parameter value. Press ENT
to confirm the change.
Checking System Status
Procedure
1.
Observe the status of the indicators located on the Rectifier Modules and ACU+. If the system is
operating normally, the status of these is as shown in
Table 6:
Status and Alarm Indicators
Component
Indicator
Normal State
Rectifier
Modules
Power
(Green)
On
Protection
(Yellow)
Off
Alarm
(Red)
Off
ACU+
Status
(Green)
On
Minor
(Yellow)
Off
Critical or Major
Alarm (Red)
Off
Configuring the ACU+ Identification of Rectifiers and Assigning Which Input Phase Is Connected to Each
Rectifier
When rectifiers are all installed prior to applying power and starting the system, the order in which the ACU+
identifies the rectifiers is by serial number (lowest serial number is Rect 1, next lowest is Rect 2, etc.). If you
prefer the ACU+ to identify the rectifiers by position in the system, perform the following procedure.
Upon power up, the ACU+ arbitrarily assigns Phase A, B, or C to each rectifier. This assignment is used to
display rectifier AC input phase voltage(s). The User may reassign the phase to each rectifier per your specific
installation by following the procedure below. (Note:
This power system is single phase only.)
Procedure
1.
With the Main screen displayed, press ENT to go to the Main Menu. Navigate to and select “Settings”
(ENT).
2.
If a password screen opens, a password must be entered to allow the User to make adjustments. If a
password was previously entered and has not yet timed out, skip this step and proceed to step 3).
Otherwise, to enter a password, with the cursor at the User Name field (default is “Admin”), press the
down arrow key to move cursor down to the password line. Press ENT. “0” is highlighted. Press the up
arrow key once to change the “0” to”1” (default password is “1”), then press ENT twice. (
Note:
If you
have been assigned a unique User Name and password, follow this procedure to enter these.
)