5 USING THE WEB INTERFACE
Use the Liqui-tect web user interface (UI) to configure leak-detection and to monitor system status.
NOTE: The default IP address for the LP6000 controller is 169.254.24.7. This may have been changed.
If the address has been changed, use the following steps to get the IP address for the web interface.
Verify the IP address in use:
•
See
on page 24 to verify the IP address.
To log-in to the web UI:
1. Open a web browser, and enter the LP6000 controller's IP address in the address bar.
The authentication dialog opens.
2. Enter a User Name and Password, and click
Log In
.
The default user name and password are as follows. This may have been changed. Contact
your Liqui-tect system administrator for the assigned user name and password.
•
Default user name: Liebert (case sensitive)
•
Default password:
Read-only access: There is no default password, leave the field blank.
Read/Write access: Liebert (case sensitive)
The web UI opens to the
5.1 Liqui-tect Home Page
The home page displays system information, including current alarm status, the reported length of the
connected leak-detection cable, the last time an alarm activated, and the running system up-time. The
image can be linked to interactive floor maps.
•
To access the home page, click
Home
on the menu bar.
Vertiv
| Liqui-tect LP6000 Installer/User Guide |
35
Summary of Contents for Liqui-tect LP6000
Page 1: ...Liqui tect LP6000 Leak detection System Leak detection System Installer User Guide...
Page 18: ...Vertiv Liqui tect LP6000 Installer User Guide 18 This page intentionally left blank...
Page 20: ...Vertiv Liqui tect LP6000 Installer User Guide 20 This page intentionally left blank...
Page 34: ...Vertiv Liqui tect LP6000 Installer User Guide 34 This page intentionally left blank...
Page 60: ...Vertiv Liqui tect LP6000 Installer User Guide 60 This page intentionally left blank...
Page 74: ...Vertiv Liqui tect LP6000 Installer User Guide 74 This page intentionally left blank...
Page 76: ...Vertiv Liqui tect LP6000 Installer User Guide 76 This page intentionally left blank...
Page 80: ...Vertiv Liqui tect LP6000 Installer User Guide 80 This page intentionally left blank...
Page 81: ......