FIELD
DESCRIPTION
Zone #
Number designating a zone.
Label
Descriptive label for the zone displayed in notifications and event logs. 30-character limit.
End Distance
Distance on the leak-detection cable at the end of the zone. Zone #1 always starts at 0 (zero), and the end of the
zone is designated by distance from start. The each subsequent zone starts at the End Distance of the previous
zone.
Table 6.5 LCD Virtual Zone fields
4.6.4 Configuring Slave Zones on the Touchscreen
If slave controllers are connected to the LP6000, use Slave Zones to configure control of the slaved
devices.
To configure slave zones:
1. On the LCD display, touch
Setup
, enter a password if needed, and touch the enter key.
The Setup menu opens.
2. Touch
Up
/
Down
to highlight Slave Zone, and touch
Select
.
The Slave Zone Settings menu opens.
3. Touch
Up
/
Down
to highlight the zone to configure, and touch
Select
.
The Slave Zone Setup menu opens.
4. Touch
Up
/
Down
to highlight the setting to configure (described in the following table), and
touch
Select
.
See
Using the Keyboard and Selecting Settings
on page 26 to update the setting.
Vertiv
| Liqui-tect LP6000 Installer/User Guide |
28
Summary of Contents for Liqui-tect LP6000
Page 1: ...Liqui tect LP6000 Leak detection System Leak detection System Installer User Guide...
Page 18: ...Vertiv Liqui tect LP6000 Installer User Guide 18 This page intentionally left blank...
Page 20: ...Vertiv Liqui tect LP6000 Installer User Guide 20 This page intentionally left blank...
Page 34: ...Vertiv Liqui tect LP6000 Installer User Guide 34 This page intentionally left blank...
Page 60: ...Vertiv Liqui tect LP6000 Installer User Guide 60 This page intentionally left blank...
Page 74: ...Vertiv Liqui tect LP6000 Installer User Guide 74 This page intentionally left blank...
Page 76: ...Vertiv Liqui tect LP6000 Installer User Guide 76 This page intentionally left blank...
Page 80: ...Vertiv Liqui tect LP6000 Installer User Guide 80 This page intentionally left blank...
Page 81: ......