LIEBERT® OUTDOOR CONTROL ENCLOSURE™

Quick Installation Guide

  

590-1734-501A/SL-10060_REV5_9-17

  

7-9/16”

(192mm)

ELECTRICAL CONNECTIONS

WARNING:

 Arc flash and 

electric shock hazard. Open all 

local and remote electric power-

supply disconnect switches, verify 

with a voltmeter that power is off 

and wear appropriate OSHA-

approved personal protective 

equipment per NFPA 70E before 

working within the electric control 

enclosure. Installer must provide a 

remote, electric-power disconnect 

switch and earth ground to unit per 

NEC, CEC and local codes as 

applicable. Failure to comply can 

cause injury or death.

Hazardous-voltage 

Power-supply Wiring

Wire per NEC and local codes.
Hazardous-voltage electrical 

service is required at the location 

of the control enclosure. Use the 

knockouts provided at the bottom 

of the enclosure. This power 

supply does not have to be the 

same voltage as the Liebert indoor 

unit. This separate power source 

may be 110V, 208V, 230V, 460V or 

575V, single-phase or three-phase, 

60Hz; or it may be 200V, 230V, 

380V or 415V, single-phase or 

three-phase, 50 Hz as appropriate.

Extra-low-voltage Control 

Wiring

Control interlock between the 

control enclosure and the indoor 

unit(s) or other source(s) is 

required. Multiple indoor units may 

be connected in parallel if the 

controlled pumps will feed them all.

•  Extra-low voltage, non-safety 

control wiring must be a 

minimum of 16 GA. (1.665 mm

2

for up to 75 ft (22.9 m), or not 

to exceed 1-V drop in the 

control line.

3-11/16”

(94mm)

20-5/16”

(516mm)

36”

(914mm)

16-13/16”

(427mm)

2-13/16”

(71mm)

37-9/16”

(954mm)

3-11/16”

(94mm)

20-5/16”

(516mm)

21”

(533mm)

16-13/16”

(427mm)

2-13/16”

(71mm)

22-9/16”

(573mm)

7-9/16”

(192mm)

BOTTOM 

VIEW

BOTTOM 

VIEW

7/8” 

1-1/8” Ø

1-3/8” Ø

1-3/4” Ø

7/8” Ø

7/8” Ø

7/8” Ø

1-1/8” Ø

1-3/8” Ø

1-1/8” Ø

7/8” Ø

1-1/8” Ø

1-3/8” Ø

1-3/4” Ø

7/8” Ø

7/8” Ø

7/8” Ø

1-1/8” Ø

1-3/8” Ø

1-1/8” Ø

Dimensions and Knockouts for 36-in. Models

Dimensions and Knockouts for 21-in. Models

Summary of Contents for Liebert

Page 1: ...witch and earth ground to unit per NEC CEC and local codes as applicable Failure to comply can cause injury or death NOTICE Risk of water leaks Can cause equipment damage NOTE To flush mount the back of the enclosure the adjustable brackets can be inverted Refer to the Dimensions drawings on the following page NOTE Alternate mounting locations are on a secure wall or building surface Use the provi...

Page 2: ...t have to be the same voltage as the Liebert indoor unit This separate power source may be 110V 208V 230V 460V or 575V single phase or three phase 60Hz or it may be 200V 230V 380V or 415V single phase or three phase 50 Hz as appropriate Extra low voltage Control Wiring Control interlock between the control enclosure and the indoor unit s or other source s is required Multiple indoor units may be c...

Page 3: ...ll for cooling the compressor contactor and or the Econ O Coil relay in the Liebert unit is energized The relay and contactor are in the Liebert indoor evaporator section Each compressor contactor has a side switch wired in parallel with the Econ O Coil relay and is responsible for closure of the low voltage pump control circuit This low voltage circuit has a series of contactors relays selector s...

Page 4: ...missions Specifications are subject to change without notice LIEBERT OUTDOOR CONTROL ENCLOSURE Quick Installation Guide 4 1734 501A SL 10060_REV5_9 17 TECHNICAL SUPPORT AND SERVICE Vertiv Services Inc 24x7 dispatch of technicians for all products 1 800 543 2378 Liebert Thermal Management Products 1 800 543 2778 Liebert Channel Products 1 800 222 5877 Liebert AC and DC Power Products 1 800 543 2378...

Reviews: