Vertiv | Liebert XDH | User Manual
27
Mechanical Installation (Site Preparation)
No. Description
No.
Description
1
Water trap
3
Charge water
2
Condensate drain pan
Figure 3-15 Draining the Condensate Water
•
Do not cut off the bracket of the water trap, otherwise the drainage of the condensed water will be affected.
• Prior to startup, charge water in the water trap to avoid blowing the water.
•
To avoid water leakage, use a Teflon sealing tape between flexible pipes and connectors.
3.5.Post-Installation Arrangements
After the installation of the unit, the piping connections along with all the fasteners of the XDH unit must
be inspected and fastened before commissioning. The air baffles and the installation holes on the top of the
cabinet must be adjusted as per the site requirements.
3.5.1.
Adjusting Air Baffles
Adjust the direction of the air baffle according to the installation position of the XDH precision air conditioner
so as to guide the airflow towards left or right side. The baffle consists of several blocks the direction of which
can be adjusted by removing the screws on the left and right sides of the grille, rotating it by 180 degrees and
then installing again to change the airflow direction. The mounting screws of the air baffle is shown in