4.3 Liebert XDCF Installation Considerations
No cutting or drilling is required to attach the modules to the rear of the Egenera BladeFrame cabinet. All
mounting holes, slots and pins required are fabricated at the factory.
Liebert XDCF modules attach beside the power modules on the rear of the Egenera BladeFrame (see
Figure 4.3 below).
Figure 4.3 Liebert XDCF module mounting locations
4.4 Liebert XDCF Piping Connection Methods and Points
The assembly and connection means used for piping in the Liebert XD system are the same as those used
in conventional refrigeration systems. Observe all standard practices during installation and startup to
prevent damage and contamination.
Supply piping connection is 1/2" OD copper pipe, and return piping connection is 5/8" OD copper. Both
supply and return fittings are one-shot connections. These fittings contain pressurized R-134a refrigerant
inside the Liebert XDCF.
Risk of explosive discharge. Can cause death, injury and equipment damage.
Vertiv
| Liebert® Xtreme Density™ System Design Manual |
67
Summary of Contents for Liebert XD Series
Page 1: ...Liebert Xtreme Density System Design Manual...
Page 18: ...Vertiv Liebert Xtreme Density System Design Manual 18 This page intentionally left blank...
Page 20: ...Vertiv Liebert Xtreme Density System Design Manual 20 This page intentionally left blank...
Page 66: ...Figure 4 2 Overall dimensions Vertiv Liebert Xtreme Density System Design Manual 66...
Page 88: ...Figure 4 21 Liebert XDV dimensions Vertiv Liebert Xtreme Density System Design Manual 88...
Page 152: ...Vertiv Liebert Xtreme Density System Design Manual 152 This page intentionally left blank...
Page 166: ...Figure 7 7 Modules on a single chain Vertiv Liebert Xtreme Density System Design Manual 166...
Page 167: ...Figure 7 8 Modules on two chains Vertiv Liebert Xtreme Density System Design Manual 167...
Page 182: ...Vertiv Liebert Xtreme Density System Design Manual 182 This page intentionally left blank...
Page 199: ......