Figure 3.31 CANbus cable wiring
Length ft (m)
Part #
3 (0.9)
300157G10
6 (1.8)
300157G1
10 (3.0)
300157G2
15 (4.6)
300157G11
20 (6.1)
300157G3
30 (9.1)
300157G4
60 (18.3)
300157G5
90 (27.4)
300157G8
120 (36.6)
300157G7
150 (45.7)
300157G8
Table 3.21 CANbus cable part numbers
Plan wiring runs for U2U communication when designing the layout of the conditioned space. In addition
to following general good wiring practices, take these precautions:
•
Keep control and communication cables away from power cables to prevent electromagnetic
interference.
•
Do not bend cables to less than four times the diameter of the cable.
•
Do not deform cables when securing them in bundles or when hanging them.
•
Keep cables away from devices that can introduce noise into them, such as machines,
fluorescent lights and electronics.
•
Avoid stretching cables; tension when pulling cables should not exceed 25 pounds (11kg) of
pulling tension.
•
Do not secure cables with any method that might damage them. Use approved hangers, such
as those for telephone wire or RG-6 coaxial cable, available at most hardware stores.
3.27.2 CANbus Cable Length in a Network
The maximum total length of cable that can be used in a CANbus network differs by the type of Liebert
XD cooling module as shown in Table 3.22 on the next page.
Vertiv
| Liebert® Xtreme Density™ System Design Manual |
61
Summary of Contents for Liebert XD Series
Page 1: ...Liebert Xtreme Density System Design Manual...
Page 18: ...Vertiv Liebert Xtreme Density System Design Manual 18 This page intentionally left blank...
Page 20: ...Vertiv Liebert Xtreme Density System Design Manual 20 This page intentionally left blank...
Page 66: ...Figure 4 2 Overall dimensions Vertiv Liebert Xtreme Density System Design Manual 66...
Page 88: ...Figure 4 21 Liebert XDV dimensions Vertiv Liebert Xtreme Density System Design Manual 88...
Page 152: ...Vertiv Liebert Xtreme Density System Design Manual 152 This page intentionally left blank...
Page 166: ...Figure 7 7 Modules on a single chain Vertiv Liebert Xtreme Density System Design Manual 166...
Page 167: ...Figure 7 8 Modules on two chains Vertiv Liebert Xtreme Density System Design Manual 167...
Page 182: ...Vertiv Liebert Xtreme Density System Design Manual 182 This page intentionally left blank...
Page 199: ......