Refrigerant Charge, lb/foot (kg/m)
Hard-Piped Connector Length and Diameter
0.08 (0.12)
1/2" OD Liebert XDH/Liebert XDO/Liebert XDR/Liebert XDV supply connector actual length
0.13 (0.19)
5/8" OD copper tubing Liebert XDV supply connector actual length
0.26 (0.39)
7/8" OD Liebert XDO/Liebert XDH/Liebert XDR supply connector actual length
0.02 (0.03)
5/8" OD copper tubing Liebert XDV return connector actual length
0.04 (0.06)
7/8" OD copper tubing Liebert XDV return connector actual length
0.04 (0.06)
7/8" OD copper tubing Liebert XDH/Liebert XDO/Liebert XDR return connector actual length
0.07 (0.1)
1-1/8" OD copper tubing Liebert XDH/Liebert XDO/Liebert XDR return connector actual length
Table 3.16 R-134a refrigerant charge for hard-piped connector lines to and from any model
Liebert XDH/Liebert XDO/Liebert XDV
Refrigerant Charge, lb. (kg)
Metal Flex Pipe Connector Length
Supply Line Diameter 1/2"
0.3 lb. (0.14)
4 ft. Flex Pipe All Liebert XD Cooling Module
0.5 lb. (0.23)
6 ft. Flex Pipe All Liebert XD Cooling Module
0.7 lb. (0.32)
8 ft. Flex Pipe All Liebert XD Cooling Module
0.8 lb. (0.36)
10 ft. Flex Pipe All Liebert XD Cooling Module
Return Line Diameter 5/8"
0.01 lb. (0.01)
4 ft. Flex Pipe existing Liebert XDCF/Liebert XDV systems
0.02 lb. (0.01)
6 ft. Flex Pipe existing Liebert XDCF/Liebert XDV systems
0.03 lb. (0.01)
8 ft. Flex Pipe existing Liebert XDCF/Liebert XDV systems
0.03 lb. (0.01)
10 ft. Flex Pipe existing Liebert XDCF/Liebert XDV systems
Return Line Diameter 1"
0.13 lb. (0.06)
4 ft Flex Pipe Liebert XDH/Liebert XDO/Liebert XDR supply
0.2 lb. (0.09)
6 ft Flex Pipe Liebert XDH/Liebert XDO/Liebert XDR supply
0.27 lb. (0.12)
8 ft Flex Pipe Liebert XDH/Liebert XDO/Liebert XDR supply
0.33 lb. (0.15)
10 ft Flex Pipe Liebert XDH/Liebert XDO/Liebert XDR supply
Table 3.17 R-134a refrigerant charge for Flex Pipe connector lines to and from any model
Liebert XDO/Liebert XDH/Liebert XDV/Liebert XDCF
3.23.2 Calculating Refrigerant R134a Charge—Example
Using Table 3.14 on the previous page,Table 3.15 on the previous page,Table 3.16 above andTable 3.17
above, calculate the refrigerant charge of the individual sections of your Liebert XD system. Add the
calculated charge amounts to determine the amount of R-134a refrigerant required for one system
combining a Liebert XDP with Liebert XD cooling modules (Liebert XDCF, Liebert XDH, Liebert XDO,
Liebert XDR and Liebert XDV). The example below combines one Liebert XDP with 20 Liebert XDV8
cooling modules.
Vertiv
| Liebert® Xtreme Density™ System Design Manual |
57
Summary of Contents for Liebert XD Series
Page 1: ...Liebert Xtreme Density System Design Manual...
Page 18: ...Vertiv Liebert Xtreme Density System Design Manual 18 This page intentionally left blank...
Page 20: ...Vertiv Liebert Xtreme Density System Design Manual 20 This page intentionally left blank...
Page 66: ...Figure 4 2 Overall dimensions Vertiv Liebert Xtreme Density System Design Manual 66...
Page 88: ...Figure 4 21 Liebert XDV dimensions Vertiv Liebert Xtreme Density System Design Manual 88...
Page 152: ...Vertiv Liebert Xtreme Density System Design Manual 152 This page intentionally left blank...
Page 166: ...Figure 7 7 Modules on a single chain Vertiv Liebert Xtreme Density System Design Manual 166...
Page 167: ...Figure 7 8 Modules on two chains Vertiv Liebert Xtreme Density System Design Manual 167...
Page 182: ...Vertiv Liebert Xtreme Density System Design Manual 182 This page intentionally left blank...
Page 199: ......