7.9.2 CANbus Maximum Length
The CANbus network (the sum of the two CANbus chains) has a maximum length limitation.
•
If the Liebert XDP or Liebert XDC with iCOM does not have a CAN Isolator, the maximum
distance is 150 ft. (46m) total network without measuring the final device voltage. The 150 ft.
(46m) total must also include the remote temperature and humidity sensor cable lengths.
•
If the Liebert XDP or Liebert XDC contains a CAN Isolator, the maximum distance is 300 ft.
(91m). To exceed this length, the final device voltage must be measured.
7.10 CANbus Cables
The Liebert XDP may be connected to the Smart Modules with a CANbus cable. The shielded cable
consists of three pairs of twisted wires with a 6-pin RJ12 connector.
NOTICE
Risk of improper wiring. Can cause equipment damage.
Mismatching wire pins at the RJ12 connection will damage the CAN device. Extreme caution should be
taken when making cables.
Figure 7.9 CANbus cable
Liebert Part #
Dimension A ft. (m)
300157G1
6 (1.8)
300157G2
10 (3)
300157G3
20 (6)
300157G4
30 (9.1)
300157G5
60 (18.3)
300157G6
90 (27.4)
300157G7
120 (36.6)
300157G8
150 (45.7)
300157G9
6.25 (1.9)
300157G10
3 (0.9)
Table 7.3 CANbus cable lengths and part numbers
Vertiv
| Liebert® Xtreme Density™ System Design Manual |
168
Summary of Contents for Liebert XD Series
Page 1: ...Liebert Xtreme Density System Design Manual...
Page 18: ...Vertiv Liebert Xtreme Density System Design Manual 18 This page intentionally left blank...
Page 20: ...Vertiv Liebert Xtreme Density System Design Manual 20 This page intentionally left blank...
Page 66: ...Figure 4 2 Overall dimensions Vertiv Liebert Xtreme Density System Design Manual 66...
Page 88: ...Figure 4 21 Liebert XDV dimensions Vertiv Liebert Xtreme Density System Design Manual 88...
Page 152: ...Vertiv Liebert Xtreme Density System Design Manual 152 This page intentionally left blank...
Page 166: ...Figure 7 7 Modules on a single chain Vertiv Liebert Xtreme Density System Design Manual 166...
Page 167: ...Figure 7 8 Modules on two chains Vertiv Liebert Xtreme Density System Design Manual 167...
Page 182: ...Vertiv Liebert Xtreme Density System Design Manual 182 This page intentionally left blank...
Page 199: ......