Avoid ground level sites with public access and areas that contribute to heavy snow or ice accumulations.
Utilize Piggyback drycoolers whenever interior building locations must be used. To ensure adequate air
supply, Vertiv recommends that the drycoolers be located in an area with clean air, away from loose dirt
and foreign matter that may clog the coil. In addition, drycoolers should not be located near steam, hot air
or fume exhausts. Drycoolers must not be installed in a pit, where discharge air is likely to be recirculated
through the drycooler or installed where objects restrict the air inlet free area. Also, the drycoolers should
be located no closer than 3 feet (1m) from a wall, obstruction or adjacent unit (see Figure 6.13 on the next
page).
The drycooler must be installed on a level surface to ensure proper glycol flow, venting and drainage.
For roof installation, mount the drycooler on suitable curbs or other supports in accordance with local
codes.
Allow adequate space for pump packages, expansion/compression tanks, piping and additional field
supplied devices.
When mounting pump packages, mount on level surface or suitable curbs that will allow cooling
ventilation air to enter from underneath the pump package frame and exit through the louvers.
6.9 Dimensions and Weights
Model
No. of
Fans
Net
Weight
lb (kg)
Domestic Packaging
Export Packaging
Packaged
Weight lb (kg)
Dimensions L x W
x H in (cm)
Volume
ft
3
(m
3
)
Packaged
Weight lb (kg)
Dimensions L x W
x H in (cm)
Volume
ft
3
(m
3
)
*D**880
8
2330
(1058)
2730 (1239)
184 x 37 x 97
(467 x 94 x 246)
382
(10.8)
3230 (1446)
185 x 38 x 97
(470 x 97 x 246)
395
(11.2)
*D**940
2430
(1103)
2910 (1321)
3410 (1548)
Table 6.13
Standard drycooler net weights, shipping weights, dimensions and volume, approximate
Vertiv
| Liebert® Xtreme Density™ System Design Manual |
137
Summary of Contents for Liebert XD Series
Page 1: ...Liebert Xtreme Density System Design Manual...
Page 18: ...Vertiv Liebert Xtreme Density System Design Manual 18 This page intentionally left blank...
Page 20: ...Vertiv Liebert Xtreme Density System Design Manual 20 This page intentionally left blank...
Page 66: ...Figure 4 2 Overall dimensions Vertiv Liebert Xtreme Density System Design Manual 66...
Page 88: ...Figure 4 21 Liebert XDV dimensions Vertiv Liebert Xtreme Density System Design Manual 88...
Page 152: ...Vertiv Liebert Xtreme Density System Design Manual 152 This page intentionally left blank...
Page 166: ...Figure 7 7 Modules on a single chain Vertiv Liebert Xtreme Density System Design Manual 166...
Page 167: ...Figure 7 8 Modules on two chains Vertiv Liebert Xtreme Density System Design Manual 167...
Page 182: ...Vertiv Liebert Xtreme Density System Design Manual 182 This page intentionally left blank...
Page 199: ......