Figure 6.4 Double discharge riser layout
Contact your local Liebert representative for factory approval whenever a refrigerant piping run exceeds
200 feet (60m) equivalent length or when condensers must be installed below the level of the cooling coil.
For Air-Cooled Liebert Lee-Temp / Flood Back Head Pressure Control Units Only
WARNING! Risk of explosive discharge from high-pressure refrigerant. Can cause injury or
death.
This unit contains fluids and/or gases under high pressure.
Relieve pressure before working with piping.
NOTICE
Risk of refrigerant contamination. Can cause equipment damage and operational problems.
Refrigerant R-407C is a blend of three components and must be introduced and charged from
the cylinder only as a liquid.
Vertiv
| Liebert® Xtreme Density™ System Design Manual |
124
Summary of Contents for Liebert XD Series
Page 1: ...Liebert Xtreme Density System Design Manual...
Page 18: ...Vertiv Liebert Xtreme Density System Design Manual 18 This page intentionally left blank...
Page 20: ...Vertiv Liebert Xtreme Density System Design Manual 20 This page intentionally left blank...
Page 66: ...Figure 4 2 Overall dimensions Vertiv Liebert Xtreme Density System Design Manual 66...
Page 88: ...Figure 4 21 Liebert XDV dimensions Vertiv Liebert Xtreme Density System Design Manual 88...
Page 152: ...Vertiv Liebert Xtreme Density System Design Manual 152 This page intentionally left blank...
Page 166: ...Figure 7 7 Modules on a single chain Vertiv Liebert Xtreme Density System Design Manual 166...
Page 167: ...Figure 7 8 Modules on two chains Vertiv Liebert Xtreme Density System Design Manual 167...
Page 182: ...Vertiv Liebert Xtreme Density System Design Manual 182 This page intentionally left blank...
Page 199: ......