LIEBERT® RPC2™ COMMUNICATIONS MODULE
Quick Installation Guide
2
SL20842_Rev3/590-1771-501A
7. Restarting the RPC2
Click the Save icon when
finished and click the Reboot
icon to restart the RPC2.
Disconnect the cabling at the
link port. Connect the
CAT5/5E/6 cable from the LAN
to the RPC2 communication
module’s network port.
8. Creating a Rack PDU
Array
Connect a CAT5 Ethernet cable
to the link port of the master
RPC2. Then connect the other
end of the CAT5 Ethernet cable
to the network port of a sibling
RPC2 on a second MPH2. This
rack PDU is now a sibling unit
and is accessible through the
master RPC2. Two additional
rack PDUs can be connected to
the array by following the same
cabling procedure. Each newly
added rack PDU is discovered
as the next sibling.
NOTE:
The rack PDU array
supports up to four RPC2
communication modules.
NOTE:
If the array order needs to
be changed, disconnect the
cabling for at least 30 seconds.
Then reconnect as desired. It is not
necessary to reboot or power cycle
the RPC2 communications module.
Rack PDU Array Configuration
Master
Sibling
Sibling
Sibling