Installation
•
Where the main channel pipe pressure may exceed 700 kPa (the main line pressure should be between
100 kPa to 700 kPa), a pressure reducer should be fitted.
•
Where the main pipe pressure falls below 100 kPa, a water tank and pump system should be used.
No.
Description
No.
Description
1
Inlet pipe
2
Outlet joint
Figure 2-20 Infrared Humidifier
•
Electrode Humidifier
Requirements for connecting water inlet pipe of electrode humidifier: Water inlet pipe uses 3/4” G screw-
threaded connection pipe.
Water filter and water quality detection are recommended to prevent the water quality from affecting the
normal operation of the humidifier.