21
2.6.1
Connecting I/O Cables
Connect the UPS power cables to the I/O terminal block on the UPS rear panel as shown in
.
Figure 19 Input/output cable terminals
Power Distribution Mode
There are two modes for UPS power distribution:
•
optional Maintenance Bypass Cabinet, and
•
self-distribution.
Table 3
AC currents and cables—UPS bypass input* and output
Unit
Rating
Maximum
Current (A)
75°C THW Copper
Wire (phase)
75°C THW Copper
Wire (neutral)
75°C THW Copper
Wire (Ground)
8KVA
23
10AWG
10AWG
10AWG
10KVA
28
8AWG
8AWG
10AWG
* Input sizes and values apply to dual-source configuration.
Table 4
Ring terminal part numbers
AWG (mm
2
)
10 (5.26)
8 (8.36)
6 (13.3)
Part #
McMaster-Carr:
7113K462
McMaster-Carr:
7113K444
McMaster-Carr:
7113K366
Thomas & Betts: RC10-
14
Thomas & Betts: RDV717
Thomas & Betts: RE6-14
Tyco Electronics:
1577648-1
Tyco Electronics:
132331-1
—
1.
Output
Terminals
C, B, A, N, N, pC, pB, pA
2. Input Terminals
N, N, bC, rC, bB, rB, bA, rA
3. Battery
Terminals
BAT-: Battery Negative
Terminal
BATN: Battery Neutral
Terminal
BAT+: Battery Positive
Terminal
WARNING
Risk of improper installation. Can cause equipment damage, injury and death.
After the power cables are connected, the protective cover board of the I/O terminal block
must be reinstalled to remove the electric shock hazard.
R
EPO
Summary of Contents for Liebert ITA2-08KRT208
Page 1: ...Liebert ITA2 8 10kVA 60Hz 208 220V Three Phase UPS User Manual...
Page 40: ...Vertiv Liebert ITA2 User Manual 34 Figure 31 Status page menus...
Page 70: ...Vertiv Liebert ITA2 User Manual 64 NOTES...
Page 71: ...Vertiv Liebert ITA2 User Manual 65...
Page 72: ...Vertiv Liebert ITA2 User Manual 66...
Page 73: ......