LIEBERT® EXS™ UPS 208/220 ‑V 30 KVA

Quick Installation Guide

  

590-1971-501A/SL-70330_REV0

 

POWER WIRING AND 

CONDUIT

When connecting wiring, follow the 

local wiring regulations, and take the 

environment situation into account.

NOTE:

 The conduit size and wiring 

method must be in accordance with 

all local, regional and national codes 

and regulations, including NEC 

ANSI/NFPA 70.

The maximum current for operating 

modes, the recommended wire 

sizes, and the recommended power 

cables and plugs are listed in Tables 

1 to 3, above, and are based upon an 

86°F (30°C) ambient temperature.

Lock-out and tag before   

you begin

Ensure that the feeder breakers are 

open and locked, and tagged to 

prevent inadvertent operation by 

unauthorized personnel.

HARDWIRE INPUT/OUTPUT 

CONNECTIONS
Connecting a 

single-input configuration

1. On the rear panel of the UPS,

remove the upper conduit-

entry panel, punch holes for

the conduit, connect the

conduit to the panel, and

re-install the conduit-entry

panel.

2. Remove the lower cover plate

to access the terminal blocks,

shown in the “Terminal-block

Connections” illustration on the

next page.

3. Leave the factory-installed

single-input jumpers on the

input terminal blocks and make

the following input connections

from the upstream feeder

panel to the input terminal:
• Phase A to rA
• Phase B to rB

• Phase C to rC
• Neutral to inN
• Ground cable to PE

4. Make the following output

connections from the UPS

output terminal to the

downstream distribution-panel

main lug breaker:
• oA to Phase A
• oB to Phase B
• oC to Phase C
• oN to neutral bus
• PE to ground bus

5. Torque phase conductor

connections to 50 lb-in, and

neutral and ground conductor

connections to 126 lb-in.

6. Reinstall the terminal-block

cover plate.

Connecting a 

dual-input configuration

Table 3 Recommended lug sizes for phase, neutral and ground conductors

6 AWG (13.3 mm

2

)

1/0 AWG (53.5 mm

2

)

2/0 (67.4 mm

2

)

Part Number

McMaster-Carr: 7113K366

Thomas & Betts: 54152NT

Thomas & Betts: 54157NT

Thomas & Betts: RE6-14

Recommended Torque

50 lb-in. / 4.2 lb-ft . / 5.6 Nm

Table 3 Recommended lug sizes for external battery conductors

6 AWG (13.3 mm

2

)

1/0 AWG (53.5 mm

2

)

2/0 (67.4 mm

2

)

Part Number

Thomas & Betts: RE6-516

Thomas & Betts: 54153NT

Thomas & Betts: 54158NT

Thomas & Betts: CTL6-516

Recommended Torque

126 lb-in. / 10.5 lb-ft . / 14.2 Nm

Table 1 Currents and Wire Size 

— UPS rectifier input

Unit Rating

Maximum Input 

Current (A)

Recommended OPD,  

Amp Trip

75°C THW Copper Wire (phase)

Number of Cables per phase:1

75°C THW Copper Wire 

neutral)

Number of Cables:1

75°C THW Copper Wire 

(ground)

Number of Cables: 1

30 kVA/kW

105

150

2/0

2/0

6 AWG

Table 2 AC Currents and Wire Size 

— UPS bypass input* and output

Unit Rating

Maximum Input 

Current (A)

Recommended OPD,  

Amp Trip

75°C THW Copper Wire (phase)

Number of Cables  per phase:1

75°C THW Copper Wire 

(neutral)

Number of Cables:1

75°C THW Copper Wire 

(ground)

Number of Cables: 1

30 kVA/kW

83

125

1/0

1/0

6 AWG

*Bypass input for dual-input configurations only.