![Vertiv Liebert EXM MBC User Manual Download Page 49](http://html1.mh-extra.com/html/vertiv/liebert-exm-mbc/liebert-exm-mbc_user-manual_1008224049.webp)
Vertiv
™
| Liebert
®
EXM
™
MBC Installation Manual |
43
3.2
Torque Requirements
All electrical connections must be tight.
Tables 21
and
22
provide the torque values for the connections to the Liebert EXM MBC. Use
these values unless the equipment is labeled otherwise.
250kcmil
54174
60154
300kcmil
54179
60160
350kcmil
256-30695-112
—
400kcmil
256-30695-1403
—
500kcmil
256-30695-339
—
Table 20
Recommended lug sizes (Compression Type) M12, 1/2" bolt
Cable Size
T&B Copper
Two-Hole
T&B Aluminum
Two-Hole
#6AWG
256-030695-
868
—
#4AWG
256-030695-
733
—
#2-3AWG
54811BE
—
#1AWG
54857BE
—
#1/0AWG
256-30695-593
—
#2/0AWG
54862BE
60238
#3/0AWG
54864BE
60244
#4/0AWG
54866BE
60250
250kcmil
54868BE
60256
300kcmil
54870BE
60262
350kcmil
54872BE
60267
400kcmil
54874BE
60269
500kcmil
54876BE
60273
600kcmil
54878BE
60275
700kcmil
54879BE
60277
750kcmil
54880BE
60278
Table 21
Busbar torque for power wiring
Bolt Shaft Size
Torque
Lb-in (Nm)
3/8" (M10)
192 (22)
1/2" (M12)
428 (48)
Table 22
Terminal block torque with compression lugs for control wiring
AWG Wire Size
or Range
Torque
Lb-in (Nm)
#22 - #14
3.5 to 5.3
(0.4 to 0.6)
Table 19
Recommended lug sizes (compression type) M10, 3/8" bolt
Cable Size
T&B Copper
One Hole
T&B Aluminum
One Hole