3 SYSTEM DATA
3.1 Capacity and Performance Data
Air-side
∆
T
Supply-air
Temperature
Return-air
Temperature
Outdoor
Temperature
Air flow
6
Net Sensible
Capacity
Input
Power
SCOP
°F
°F
°C
°F
°C
°F
°C
CFM
CMH
kW
kBtu/hr
kW
–
20
70
21
90
32
95
35
40,500 68,810
248.4
848
97
2.6
74
23
94
34
95
35
43,000 73,057
259.7
886
101.5
2.6
25
70
21
95
35
95
35
34,000 57,766
258.5
882
88.3
2.9
74
23
99
37
95
35
36,000
61,164
272
928
91.8
3
1.
Total Cooling Capacity is not shown because the DA250 is 100% sensible.
2.
Capacity data is rated and factory certified per ASHRAE 127-2007 with a 5% tolerance.
3.
For downflow, bottom-discharge options, consult the factory.
4.
Quantity of Fans is 3, External Static pressure 0.1 in. and Dewpoint of 52.3°F.
5.
For return-air temperatures outside the range shown, please consult factory.
6.
Maximum air-flow calibration voltage must be adjusted based on the required air flow. See Table 3.4 on the next page,
for values.
Table 3.1 Capacity data for 60-Hz, Downflow, horizontal-discharge models
Air-side
∆
T
Supply-air
Temperature
Return-air
Temperature
Outdoor
Temperature
Air flow
6
Net Sensible
Capacity
Input
Power
SCOP
°F
°F
°C
°F
°C
°F
°C
CFM
CMH
kW
kBtu/hr
kW
–
20
70
21
90
32
95
35
36,000
61,165
220
751
74.1
3.0
74
23
94
34
95
35
38,000 64,560
231
788
77.4
3.0
25
70
21
95
35
95
35
30,600 52,000
232
792
68.0
3.4
74
23
99
37
95
35
32,500
55,225
243
829
70.5
3.5
1.
Total Cooling Capacity is not shown because the DA250 is 100% sensible.
2.
Capacity data is rated and factory certified per ASHRAE 127-2007 with a 5% tolerance.
3.
For downflow, bottom-discharge options, consult the factory.
4.
Quantity of Fans is 3, External Static pressure 0.1 in. and Dewpoint of 52.3°F.
5.
For return-air temperatures outside the range shown, please consult factory.
6.
Maximum air-flow calibration voltage must be adjusted based on the required air flow. See Table 3.4 on the next page,
for values.
Table 3.2 Capacity data for 50-Hz, Downflow, horizontal-discharge models
3 System Data
17
Summary of Contents for Liebert DSE
Page 10: ...Vertiv Liebert DSE System Design and User Guide 10 This page intentionally left blank ...
Page 16: ...Vertiv Liebert DSE System Design and User Guide 16 This page intentionally left blank ...
Page 20: ...Vertiv Liebert DSE System Design and User Guide 20 This page intentionally left blank ...
Page 22: ...Vertiv Liebert DSE System Design and User Guide 22 This page intentionally left blank ...
Page 24: ...Vertiv Liebert DSE System Design and User Guide 24 This page intentionally left blank ...
Page 32: ...Vertiv Liebert DSE System Design and User Guide 32 This page intentionally left blank ...
Page 36: ...Vertiv Liebert DSE System Design and User Guide 36 This page intentionally left blank ...
Page 46: ...Vertiv Liebert DSE System Design and User Guide 46 This page intentionally left blank ...
Page 50: ...Vertiv Liebert DSE System Design and User Guide 50 This page intentionally left blank ...
Page 52: ...Vertiv Liebert DSE System Design and User Guide 52 This page intentionally left blank ...
Page 66: ...Vertiv Liebert DSE System Design and User Guide 66 This page intentionally left blank ...
Page 68: ...Vertiv Liebert DSE System Design and User Guide 68 This page intentionally left blank ...
Page 99: ...Vertiv Liebert DSE System Design and User Guide 70 This page intentionally left blank ...
Page 119: ...Vertiv Liebert DSE System Design and User Guide ...