3.5.1 Cooling
Table 3.2 below, provides the recommended maximum and minimum return-air temperature and dew-point conditions for
the DSE Packaged Solution Applications.
Control Settings
DP400F
DP400R
DP400B
DP500F
DP500B
DP500R
Maximum Return Air Temperature
105°F (40°C)
105°F (40°C)
105°F (40°C)
Minimum return-air temperature
85°F (29°C)
95°F (35°C) *
95°F (35°C) *
Maximum dew point
59°F (15°C)
52°F (11°C)
52°F (11°C)
Maximum Supply-Air Setpoint
80°F (27°C)
80°F (27°C) *
80°F (27°C) *
Minimum Supply Air Control Setpoint
68°F (20°C)
70°F (21°C)
75°F (24°C)
*Note: DP500 minimum air-side temperature differential at full load is 25°F (14°C)
Table 3.2 Application Envelope for DP400/500
Operating outside this envelope can decrease equipment reliability.
NOTE: When running above 77°F (25°C) supply-air temperature, the superheat readings on the refrigeration circuits
may be higher than 13°F (7.2°C). The EEVs will run out of stroke and limit mass flow, which will result in higher than
normal superheat.
3.6 Unit Weights
Model
Weight, lb (kg)
Perimeter
23,500 (10,659)
Rooftop
25,500 (11,567)
Rooftop Draw Through
25,500 (11,567)
Table 3.3 DSE400 Unit Weights
Model
Weight, lb (kg)
Perimeter
224,000 (10,886)
Rooftop
26,000 (11,793)
Rooftop Draw Through
26,000 (11,793)
Table 3.4 DSE500 Unit Weights
Vertiv | DSE Packaged Solution Installer/User Guide
16
Summary of Contents for Liebert DSE Packaged 400
Page 1: ...Liebert DSE Packaged Solution Installer User Guide 400 kW to 500 kW...
Page 24: ...Vertiv DSE Packaged Solution Installer User Guide 20 This page intentionally left blank...
Page 32: ...Vertiv DSE Packaged Solution Installer User Guide 28 This page intentionally left blank...
Page 34: ...Vertiv DSE Packaged Solution Installer User Guide 30 This page intentionally left blank...
Page 36: ...Vertiv DSE Packaged Solution Installer User Guide 32 This page intentionally left blank...
Page 68: ...Vertiv DSE Packaged Solution Installer User Guide 64 This page intentionally left blank...
Page 103: ...Vertiv DSE Packaged Solution Installer User Guide 66 This page intentionally left blank...
Page 104: ...Vertiv DSE Packaged Solution Installer User Guide...