Figure A.1 L-Series Inline Power Monitoring Unit
A.2 Detachable power supply cords
L-Series Inline Power Monitoring Units may optionally be configured with an AC Inlet for connection to AC
Mains power. Use only detachable power supply cords of the appropriate size and type, as stated below,
with the unit. Use only with light PVC sheathed flexible cords (according to IEC 60227) or ordinary tough
rubber-sheathed flexible cords (according to IEC 60245) that terminate in an attachment plug meeting
local/national code requirements.
For Global units use a minimum 1.5 mm2 nominal conductor cross-sectional area detachable power supply
cord with ratings of 300 V and 75 °C. The power supply cord cable designation should be H03VV-F,
H03VVH2-F, or better.
For North American units use a minimum 14 AWG power supply cord with ratings of 300 V and 75 °C. The
power supply cord cable designation should be SJT or better.
To install an L-Series inline power monitoring unit:
NOTE: Please visit http://www.VertivCo.com/ComplianceRegulatoryInfo for important safety
information prior to installation.
1.
Using the appropriate hardware, mount the In-Line Meter to the rack.
2. Plug the In-Line Meter into de-energized branch circuit receptacle.
3. Connect the external device to the In-Line Meter’s output outlet or connector.
4. Turn on the branch circuit to energize the In-Line Meter.
5. Power on the external device.
NOTE: Branch Circuit should be sized based on the In-Line Meter’s nameplate electrical rating. For
North American units, the branch circuit should have a current rating equal to 125% of the unit’s
nameplate current rating. For global units, the branch circuit should have a current rating equal to the
unit’s nameplate current rating.
Vertiv™ | Basic Rack PDU Installer/User Guide
20
Summary of Contents for Geist BR Series
Page 1: ...Geist Basic Rack PDU Installer User Guide ...
Page 4: ...Vertiv Basic Rack PDU Installer User Guide ii This page intentionally left blank ...
Page 11: ...Figure 2 2 Mini L Bracket 2 Installation 7 ...
Page 12: ...Figure 2 3 Vertical Extension Bracket Vertiv Basic Rack PDU Installer User Guide 8 ...
Page 13: ...Figure 2 4 Tool less Mounting Hardware 2 Installation 9 ...
Page 14: ...Figure 2 5 Tool less Full length Bracket Vertiv Basic Rack PDU Installer User Guide 10 ...
Page 15: ...Figure 2 6 Single Side mount Unit Brackets 2 Installation 11 ...
Page 17: ...Figure 2 9 Flush Mount Brackets FM Figure 2 10 Adjustable Mount Brackets AM 2 Installation 13 ...
Page 22: ...Vertiv Basic Rack PDU Installer User Guide 18 This page intentionally left blank ...
Page 26: ...Vertiv Basic Rack PDU Installer User Guide 22 This page intentionally left blank ...