Specifications
Vertiv
| Liebert
®
EXM
™
Parallel Cabinet User Manual |
31
3.2
T
ORQUE
R
EQUIREMENTS
All electrical connections must be tight.
provide the torque values for the connections to the Liebert EXM Parallel Cabinet.
Use these values unless the equipment is labeled otherwise.
Table 7
Recommended lug sizes (compression type) M10, 3/8" bolt
Cable Size
T&B Copper
One Hole
T&B Aluminum
One Hole
T&B Copper
Two-Hole
T&B Aluminum
Two-Hole
#8AWG
54132
60104-TB
—
—
#6AWG
54136
60109
256-030695-
868
—
#4AWG
54140
60114
256-030695-
733
—
#2AWG
54143
60118
54811BE
—
#1AWG
54148
60124
54857BE
—
#1/0AWG
54109
60130
256-30695-593
—
#2/0AWG
54110
60136
54862BE
60238
#3/0AWG
54111
60142
54864BE
60244
#4/0AWG
54112
60148
54866BE
60250
250kcmil
54174
60154
54868BE
60256
300kcmil
54179
60160
54870BE
60262
350kcmil
256-30695-112
—
54872BE
60267
400kcmil
256-30695-
1403
—
54874BE
60269
500kcmil
256-30695-339
—
54876BE
60273
Table 8
Busbar torque for power wiring
Bolt Shaft Size
Torque
lb-in (Nm)
3/8" (M10)
192 (22)
1/2" (M12)
428 (48)
Table 9
Terminal block torque with compression lugs for control wiring
AWG Wire Size
or Range
Torque
lb-in (Nm)
#22 - #14
3.5 to 5.3
(0.4 to 0.6)
NOTE
Refer to the manufacturer’s data for proper torque for circuit breaker power connections.