Installation Drawings
Vertiv
| Liebert
®
EXM
™
Parallel Cabinet User Manual |
17
Figure 5
Main components—600mm 2+1 Liebert EXM Parallel Cabinet,
Neutral
Busbar
Input
Busbars
NOTES
1. Control wiring and power wiring must be run in separate conduits.
2. All wiring is to be in accordance with national and local electrical codes.
3. If maintenance bypass cabinet is attached to UPS, Vertiv will supply
the interconnection cables.
Output
Busbars
(See Detail A)
MOB1
MOB3
MOB2
MIB
MBB
67"
(1702mm)
19.4"
(493mm)
2.8"
(71mm)
1.7" (43mm)
8 Typically
1.75"
(44mm)
1.75"
(44mm)
8 Typically
EXM16017
Rev. 1
DETAIL A
Phase Busbar
Connections
FRONT VIEW
Door Removed
LEFT SIDE VIEW
Panel Removed
Ground
Busbar
GROUND and
NEUTRAL BUSBAR
RIGHT SIDE
Panel Removed
TB1