Vertiv
|
eSure™ MPPT Solar Converter Module User Manual (UM1S482000E3)
|
Rev. J
12
•
Filtering:
a)
Voice Band Noise: Complies with Telcordia GR-947-CORE.
1.
Output noise according to Telcordia GR-947-CORE is <38 dBrnC typical at normal input and
30% to 80% of rated load for more than one solar converter.
2.
Psophometric noise is ≤ 2 mV typical at 30% to 80% of rated load for more than one solar
converter.
b)
Wide Band Noise: Complies with Telcordia GR-947-CORE.
1.
Wideband noise emission is <250 mV peak to peak between 0 Hz to 100 MHz, and <50 mV rms
in any 3 kHz band 10 KHz to 20 MHz.
DC Input Ratings
•
Nominal Input Voltage: 140 VDC to 400 VDC.
-
Operating Range: 120 VDC to 420 VDC.
•
Inrush Current: Peak does not exceed 1.5 times of the peak value of the maximum steady-state input
current at 25 °C, and shall not trigger the unit's internal input fault protection device(s). Charging of
input X and Y filter capacitors shall be ignored.
•
Typical Input Data:
a)
b)
Maximum Input Current: 12 A.
c)