SAG582136800
System Application Guide
Revision BA, April 8, 2020
Spec. No. 582136800 (Model 502
NGFB
)
Page 100 of 129
DC Load, C.O. Ground and Battery Connections (1-Row Distribution Cabinets)
Battery Return and C. O. Ground
All 1-Row Lists
3/8-16 studs on 1” centers
(Lug Spacing: 1” center to center)
-48V Battery
Lists AA, AB, AC (23”)
Lists FA, FB, FC (19”)
3/8-16 studs on 1” centers
(Lug Spacing: 1” center to center)
Load Return Bus Bar
1/4-20 studs on 5/8” centers
(Lug Spacing: 0.765”
center to center)
-48V Load / -48V Battery
(See specific
configurations below)
1/4-20 studs on 5/8” centers
(Lug Spacing: 0.765”
center to center)
Lists AA, AB, AC
-48V Load
Distribution
Positions (24)
Lists BA, BB, BC
-48V Load
Distribution
Positions (18)
-48V Battery
Disconnect
Positions (6)
Lists CA, CB, CC
-48V Load
Distribution
Positions (16)
-48V Battery
Disconnect
Positions (8)
Lists FA, FB, FC
-48V Load
Distribution
Positions (19)
Lists GA, GB, GC
-48V Load
Distribution
Positions (14)
-48V Battery
Disconnect
Positions (5)
Note:
23” Cabinet shown.
19” Cabinet similar.
Covers, front door &
distribution devices
omitted.