Vertiv
|
eSure™ Rectifier Module User Manual (UM1R482000e3)
|
Rev. M
11
•
Typical Input Data: 60 Hz input.
a)
b)
Maximum Input Current: Refer to
Table 3:
Typical Input Data in 60Hz Input
Nominal
Input
Voltage
Percent
of Full
Load
Input
Current
(Amperes)
Input
VA
Input
Watts
Power
Factor %
Efficiency
% Heat
Heat
Dissipation
BTU/Hr
208
0
0.34
73.20
29.60
40.43
--
100.99
25
2.39
499.90
492.40
98.50
95.27
79.46
50
4.73
985.80
978.10
99.20
95.94
135.49
75
7.09
1479.60
1474.00
99.60
95.43
229.83
100
9.54
1985.80
1982.20
99.70
94.59
365.87
110
10.31
2147.00
2142.00
99.80
94.24
420.95
120
10.35
2154.00
2149.00
99.80
93.82
452.12
240
0
0.36
105.40
31.80
30.55
--
108.5
25
2.10
504.70
491.00
97.20
95.59
73.88
50
4.11
989.30
975.90
98.60
96.18
127.19
75
6.15
1478.00
1469.60
99.30
95.73
214.10
100
8.25
1978.70
1972.20
99.60
95.08
331.10
110
8.92
2140.00
2132.00
99.60
94.78
379.70
120
8.95
2147.00
2140.00
99.60
94.32
414.71
NOTE!
System output is initially adjusted to 54.48 volts DC as measured at the system sense point at
50% of full load and nominal input. “Percent of Full Load” refers to percent of 34.5 amperes.
Table 4:
Maximum Input Current in 60Hz Input
Nominal
Input Voltage
Input Voltage
Input Current
(Amperes)
208/240
176
11.73
NOTE!
At 100% of full load with output adjusted to 58 volts DC as measured at the shelf output
terminals.