Vertiv™ NetSure™ IPE Series -48 VDC Outdoor Rectifier Installation and User Manual
Proprietary and Confidential © 2022 Vertiv Group Corp.
8
Table 1.8 Typical Input Data with 50 Hz Input
Nominal Input Voltage Percent of Full Load Input Current
(amperes)
Input VA
Input Watts
Power Factor
Efficiency %
Heat Dissipation W
120
0
0.387
46.65
16.93
16.930
25
4.233
507.03
504.05
0.994
93.60
32.271
50
8.364
999.04
996.08
0.997
94.99
49.907
75
12.647
1505.74
1501.70
0.997
94.71
79.447
100
--
--
--
--
--
--
220
0
0.622
137.00
17.33
0.231
--
17.330
25
2.319
510.03
500.44
0.981
94.39
28.060
50
4.509
991.15
984.13
0.993
96.18
37.550
75
6.740
1480.05
1474.08
0.996
96.47
52.07
100
9.793
2147.70
2143.99
0.998
96.10
83.691
240
0
0.673
16.16
17.14
0.106
--
17.140
25
2.146
515.05
500.64
0.972
94.23
28.877
50
4.143
993.62
983.46
0.990
96.27
36.691
75
6.184
1481.90
1473.96
0.995
96.55
50.905
100
8.971
2147.12
2141.83
0.998
96.23
80.7245
NOTE!
At 100% of full load with output at 56.4V as measured at the output terminals.
Table 1.9 Maximum Input Current with 50 Hz Input
Nominal Input Voltage
Input
Voltage
Input Current (Amperes)
100 VAC to 250 VAC
176 VAC
12
NOTE!
At 100% of full load with output at 56.4V as measured at the output terminals.