Chapter 1 Overview 17
ECM3 Series Outdoor Power System User Manual
Hydrogen exhausting function
For 300W air conditioner cabinet, its emergent fan functions as a hydrogen exhausting fan for a period (5 minutes by
default) at a preset hydrogen exhausting interval (24 hours by default) to dilute concentration of hydrogen in the
cabinet.
Performance parameter
The system provides two types of air conditioner for user selection, see Table 1-19 for specific parameters.
Table 1-19 Parameters of air conditioner
Type
Heating performance
Cooling
Heating
300W air conditioner
Under L35/L45 conditioner, meets 600Ah battery
heating power
In the battery compartment of general cabinet,
if the selected air conditioner with heating
function, then the inside temperature can be
heated from -40°C to -0°C within two hours; In
single battery cabinet, if the selected air
conditioner with heating function, then the
inside temperature can be heated from -20°C
to -5°C within two hours; If it needs to meet
-40°C ambient temperature, another group of
heater (630W) should be selected
1.5kW air condi
emergent ventilation
(optional)
Under L35/L45 conditioner, meets 1000W load
If the selected air conditioner with heating
function, then the inside temperature can be
heated from -40°C to -5°C within two hours
1.5 Main Features
Flexible configuration, applicable to various thermal control modes and user equipment.
Easy to disassemble and install onsite, meeting various installation site requirements.
Protection index: meet the requirement of IP45.
Lighting: LED lamp configured, easy to maintain.
Thermal control unit: adjustable according to temperature changes, energy saving.
Complete environment monitoring system: monitoring the power system, thermal control unit, and environment
parameters; uploading alarms.