12 Chapter 1 Overview
ECM3 Series Outdoor Power System User Manual
Table 1-16 Ports silkprint and description
Silkprint
Description
PE terminal
POWER 36-60VDC
Power input port, power input range: 36Vdc ~ 60Vdc
CONSOLE
Console port
12V
Output terminal of 12Vdc auxiliary power
AGND
Ground terminal of 12Vdc auxiliary power
V1+, V1M, V1-
V2+, V2M, V2-
Total battery string voltage port. V1+, V2+: positive battery terminal; V1M, V2M: battery middle
points; V1-, V2-: negative battery terminal
CH1 ~ CH8
AI1 ~ AI8, can be set to voltage, DC current or digital signal input channel
REL1 ~ REL4
Output common terminal of relays 1, 2, 3, 4
NO1 ~ NO4
Normally open node of relays 1, 2, 3, 4, can be set to normally closed node through internal
jumpers
DI1 ~ DI12
DI port, can be voltage or digital signal input channel
DI13 ~ DI16
Water detection input
COM1 ~ COM9
Serial ports 1 ~ 9, supporting RS485 communication mode
COM10
Serial ports 10, supporting RS232 communication mode
CONSOLE
Port standard: RS232; baud rate:115200bps, N, 8, 1; non-isolation
Micro SD
Micro SD card slot, max. 32G Micro SD card can be inserted into the slot to expand the storage
space of the monitoring equipment
USB
USB port, for connecting modem
LAN1/2/3/4
10M/100M self-adaptive Ethernet port
The FSU acquires power monitoring information through RS485 port, and uploads information of components such
as heat exchanger and air conditioner through internal RS485 port. The FSU universally processes and transmits the
information to user monitoring system through Ethernet remote communication port. The appearance and port
position of the FSU are shown in Figure 1-15.
GND
Power port
Console port
Battery string
voltage input port
DI port
Relay output
Smoke
Serial ports 1 ~ 10
USB port
SD card slot
Ethernet ports 1 ~ 4
Waterlogging
AI port
Figure 1-15 ECCUP appearance and port positions
For detailed technical parameters and configuration of FSU, please refer to
FSU-2808IM Monitoring Equipment
Installation And Commissioning Manual
.
Sensor Introduction
Micro switch
Each cabinet door can be configured with a micro switch. When the door is open, the system will generate a door
open alarm. The appearance of the micro switch is shown in Figure 1-16.
Figure 1-16 Appearance of micro switch