7
OPTION LEVEL
Code
Description
Range
Default
Input type selection.
TYPE
RANGE(
℃
)
RANGE(
℉
)
J
-50~1000
-58~1832
K
-50~1370
-58~2498
T
-270~400
-454~752
E
-50~950
-58~1742
B
0~1800
32~3272
R
-50~1750
-58~3182
S
-50~1750
-58~3182
N
-50~1300
-58~2372
C
-50~1800
-58~3272
D-PT
-200~850
-328~1562
J-PT
-200~600
-328~1112
LINE
-1999~9999
Refer to figure.
K
Unit of process value
:
Degrees C.
:
Degrees F.
: Engineer unit for linear input.
℃
Decimal point selection.
0000
:
No decimal point.
000.0
:
0.1 resolution
00.00
:
0.01 resolution, used for linear input only.
0.000
:
0.001 resolution, used for linear input only.
After change decimal point, please reconfirm the
parameter.
0000
000.0
00.00
0.000
0000
Output 1 control action.
: Reverse action for heating.
: Direct action for cooling.
Low limit of span or range. Set the low limit lower
than the lowest expected SV and PV display.
Full range
0
High limit of span or range. Set the high limit higher
than highest expected SV and PV display.
Full range
1000
Software filter.
0.0-99.9
10.0
Time scale for timer alarm.
Hours:Minutes;
Minutes:Seconds
00.00~99.59
00.00
Alarm 1 function. Refer to alarm function section for
detail.
If A1FU=None, it means alarm function is cancelled.
None, Hi, Lo,
dif.H, dif.L,
bd.Hi , bd.Lo
t.on, t.oFF
Alarm 1 mode. Refer to alarm mode section for
detail..
none, Stdy,
Lath, St.La
Alarm 2 function. Refer to alarm function section for
detail
none, Hi, Lo,
dif.H, dif.L,