FIRST PROGRAMMING LEVEL PARAMETERS 
CODE 

DESCRIPTION RANGE 

Default

 Control set point value   

LoLt 

 HiLt 

500 

 

Set point offset

.  This should always be left at 0 as any value here will 

create an offset in control either above or below the “actual ” setpoint.    It is 
used as a “manual reset” when the controller is used in the proportional 
control mode.

 

-1000-1000 

(-100.0-100.0) 

 

Process value offset

. This should be left at 0 as any other value will cause 

the PV display to read inaccurately by the amount either above or below the 
actual value.    This is used in applications such as double boilers where the 
PV reading is taken in a jacket and the product temperature may be a few 
degrees lower. 

-1000-2000 

(-100.0-200.0) 

 Alarm 1 set point 

-1999

9999 

10 

 Alarm 2 set point

 

-1999

9999 

10 

 Alarm 3 set point

 

-1999

9999 

10 

 
SECOND PROGRAMMING LEVEL PARAMETERS 
 
CODE 

DESCRIPTION RANGE 

Default

  Proportional band. 

Set to 0.0 for ON/OFF control mode.

   

0.0-300.0% 0.0 

 

Derivative (Rate). 

This value is automatically calculated by activating the 

Auto tune function. When

=0.0, this parameter will not appear. 

0-900sec 0 

 

Hysteresis 

for ON/OFF control on output. When

0.0 this parameter 

will not appear.

 

0-2000 

(0.0-200.0) 

 

Proportional cycle 

time of control output. When Pb = 0.0 this parameter 

will not appear.   

Set to 15 or 20 for relay output, Set to 1 or 2 for SSR 

output, Set to 0 for current output.

 

0-100sec 15 

 

Hysteresis of alarm 1.

 When 

= t.on or t.Off,  

is not 

displayed.

 

0-2000 0 

 

 

t.on or t.Off 

(Alarm 1 action with delay time)

 

99 MM. 59 SS. 

99 HH. 59MM. 

 

Hysteresis of alarm 2.

 When 

= t.on or t.Off, 

is not 

displayed. 

 

0-2000 0 

 

 

t.on or t.oFF

(Alarm 2 action with delay time)

 

99 MM. 59 SS. 

99HH. 59 MM. 

 

Hysteresis of alarm 3

. When 

= t.on or t.Off, 

 is not 

displayed.

   

0-2000 0 

 

 

t.on or t.oFF

(Alarm 3 action with delay time)

 

99 MM. 59 SS. 

99HH. 59 MM.   

1.  These

 

parameters will only be available when

0.0.             

 When  

 = 0.0.   

  will be displayed instead. 

2. 

      parameters will only be available when 

,

,

= t.on or t.Off. and 

 , 

  will be skipped 

3. 

  parameters will be available only when 

= LinE.  and 

 will be 

 

7

Summary of Contents for VD 26 Series

Page 1: ...the parameters including the Process Variable and Set Point It is fully configurable on input including PT100 RTD There are three simple steps required to get you up and running 1 Installation 2 Wiri...

Page 2: ...play will change and read Type 5 Use the up or down keys to select the input type you require 6 Now press the set key once and the display will read Type 7 Now press the set key a few times until you...

Page 3: ...ill be charged for repairing it 6 2 All controllers are Relay output as factory standard To have SSR you must especially order them with this option 7 Relay output If you are using a relay output cont...

Page 4: ...w Scale of Linear Input 1999 9999 199 9 999 9 0 0 High Scale of Linear Input 1999 9999 199 9 999 9 100 0 10 Commissioning Having correctly wired the unit you are now ready for the initial turn on 1 Tu...

Page 5: ...e next programmable parameter press for 5 seconds to move from one programming level to next 2 UP KEY Press to increase the set point or parameter value 3 DOWN KEY Press to decrease the set point or p...

Page 6: ...PROGRAMMING LEVEL PARAMETERS lst Prog Level 2nd Prog Level 3rd Prog Level Press 5 seconds Press 5 seconds Press 5 seconds 6...

Page 7: ...ON OFF control mode 0 0 300 0 0 0 Derivative Rate This value is automatically calculated by activating the Auto tune function When 0 0 this parameter will not appear 0 900sec 0 Hysteresis for ON OFF...

Page 8: ...000 58 1832 B 0 1800 32 3272 R 50 1750 58 3182 S 50 1750 58 3182 N 50 1300 58 2372 C 50 1800 58 3272 D PT 200 850 328 1652 J PT 200 600 328 1112 LINE 1999 9999 Refer to figure K Unit of process value...

Page 9: ...efer to alarm function section for detail nonE Hi Lo dif H dif L bd Hi bd Lo t on t oFF Alarm 3 mode Refer to alarm mode section for detail nonE Stdy Lath St La HH mm mm SS RS485 address 0 255 0 Commu...

Page 10: ...CTION SELECTION ALMD DESCRIPTION Normal alarm mode Startup inhibit When selected in any alarm function prevents an alarm on power up The alarm is enabled only when the process value reaches the alarm...

Page 11: ...ck correct input sensor selection Sensor break error Sensor not connected Replace sensor Check the sensor is connected correctly Keypad no function Keypads are locked Keypads defective Set to a proper...

Reviews: