background image

27D8851

26

VWFST Series Vented Gas Log Set

NOTE REGARDING VENTED PRODUCTS

This product must be installed by a licensed plumber or gas fitter 

when installed within the Commonwealth of Massachusetts.
Any  residence  with  a  direct  vent  product  must  have  a  CO 

detector installed in the residence.
Installation  of  the  fireplace  or  vented  gas  log  in  the  State  of 

Massachusetts requires the damper to be permanently removed 

or welded in the fully open position.
In addition, a naturally vented gas log may not be installed in a 

bedroom or bathroom in the State of Massachusetts.
Flex line installation must not exceed 36 inches and must have 

a T shutoff valve. 

NOTE REGARDING VENT FREE PRODUCTS

This product must be installed by a licensed plumber or gas fitter 

when installed within the Commonwealth of Massachusetts.
In  addition,  vent  free  products  may  not  be  installed  in  a 

bedroom or bathroom regardless of size or type in the State of 

Massachusetts.
Flex line installation must not exceed 36 inches and must have 

a T shutoff valve.

CARBON MONOXIDE DETECTOR REQUIREMENTS

(2) Revise  10.8.3  by  adding  the  following  additional 

requirements:
(a)  

For  all  side  wall  horizontally  vented  gas  fueled 

equipment installed in every dwelling, building or structure used 

in  whole  or  in  part  for  residential  purposes,  including  those 

owned or operated by the Commonwealth and where the side 

wall exhaust vent termination is less than seven (7) feet above 

finished  grade  in  the  area  of  the  venting,  including  but  not 

limited to decks and porches, the following requirements shall 

be satisfied:
1. 

Installation  of  carbon  monoxide  detectors. 

At  the  time 

of  installation  of  the  side  wall  horizontal  vented  gas  fueled 

equipment,  the  installing  plumber  or  gas  fitter  shall  observe 

that a hard wired carbon monoxide detector with an alarm and 

battery  back-up  is  installed  on  the  floor  level  where  the  gas 

equipment is to be installed. In addition, the installing plumber 

or gas fitter shall observe that a battery operated or hard wired 

carbon  monoxide  detector  with  an  alarm  is  installed  on  each 

additional level of the dwelling, building or structure served by 

the side wall horizontal vented gas fueled equipment. It shall be 

the responsibility of the property owner to secure the services of 

qualified licensed professionals for the installation of hard wired 

carbon monoxide detectors
 

a.  In the event that the side wall horizontally vented gas 

fueled equipment is installed in a crawl space or an attic, the 

hard  wired  carbon  monoxide  detector  with  alarm  and  battery 

back-up may be installed on the next adjacent floor level.
 

b.  In the event that the requirements of this subdivision 

can  not  be  met  at  the  time  of  completion  of  installation,  the 

owner shall have a period of thirty (30) days to comply with the 

above requirements; provided, however, that during said thirty 

(30) day period, a battery operated carbon monoxide detector 

with an alarm shall be installed.

Massachusetts Residents Only — Please read and follow these special requirements

2. 

Approved  Carbon  Monoxide  Detectors.

 

Each  carbon 

monoxide detector as required in accordance with the above 

provisions shall comply with NFPA 720 and be ANSI/UL 2034 

listed and IAS certified.
3. 

Signage.

  A  metal  or  plastic  identification  plate  shall  be 

permanently  mounted  to  the  exterior  of  the  building  at  a 

minimum height of eight (8) feet above grade directly in line with 

the exhaust vent terminal for the horizontally vented gas fueled 

heating appliance or equipment. The sign shall read, in print size 

no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY 

BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.”
4. 

Inspection.

 The state or local gas inspector of the side wall 

horizontally vented gas fueled equipment shall not approve the 

installation  unless,  upon  inspection,  the  inspector  observes 

carbon monoxide detectors and signage installed in accordance 

with the provisions of 248 CMR 5.08(2)(a)1 through 4.
(b) 

Exemptions:

 The following equipment is exempt from 248 

CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled "Equipment Not 

Required To Be Vented" in the most current edition of NFPA 54 

as adopted by the Board; and
2.  Product Approved  side  wall  horizontally  vented  gas  fueled 

equipment  installed  in  a  room  or  structure  separate  from  the 

dwelling,  building  or  structure  used  in  whole  or  in  part  for 

residential purposes.
(c)  

Manufacturer requirements — Gas Equipment Venting 

System  Provided.

 

When  the  manufacturer  of  Product 

Approved side wall horizontally vented gas equipment provides 

a  venting  system  design  or  venting  system  components  with 

the equipment, the instructions provided by the manufacturer 

for installation of the equipment and the venting system shall 

include:
1. Detailed instructions for the installation of the venting system 

design or the venting system components; and
2. A complete parts list for the venting system design or venting 

system.
(d) 

Manufacturer requirements — Gas Equipment Venting 

System Not Provided. 

When the manufacturer of a Product 

Approved  side  wall  horizontally  vented  gas  fueled  equipment 

does  not  provide  the  parts  for  venting  the  flue  gases,  but 

identifies “special venting systems,” the following requirements 

shall be satisfied by the manufacturer:
1.  The  referenced  "special  venting  system"  instructions  shall 

be  included  with  the  appliance  or  equipment  installation 

instructions; and
2. The “special venting systems” shall be Product Approved by 

the Board, and the instructions for that system shall include a 

parts list and detailed installation instructions.
(e)  

A  copy  of  all  installation  instructions  for  all  Product 

Approved side wall horizontally vented gas fueled equipment, 

all  venting  instructions,  all  parts  lists  for  venting  instructions, 

and/or all venting design

Summary of Contents for VWF18STN

Page 1: ...o not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department In...

Page 2: ...e Volcanic Rock 14 VWF18ST VWF24ST Log Placement 14 Operating Instructions 16 SPK and CVTHL kits 16 For Your Safety Read Before Lighting 16 Manual Control SPK 16 Hi Lo control CVTHL 16 Millivolt Contr...

Page 3: ...damper be permanently removed or welded in the full open position In addition a naturally vented gas log may not be installed in a bedroom or bathroom in the Commonwealth of Massachusetts Flex line in...

Page 4: ...nown as wellhead gas Model A B C D VWF18STN 20 20 18 16 VWF24STN 26 26 18 16 Figure 1 Minimum Hearth Dimensions GAS pressures Natural Propane LP Max Gas Inlet Pressure 10 0 w c 13 0 w c Min Gas Inlet...

Page 5: ...e all parts in good condition ITEMS REQUIRED FOR INSTALLATION Ensure that the following items are available before pro ceeding with installation External regulator for propane L P G only Shutoff valve...

Page 6: ...replace firebox Depth of fireplace firebox Refer to Table Figure 2 NOTE Noncombustible material such as refractory brick may be used to line the floor of the fireplace in order to raise the height of...

Page 7: ...rally vented gas log may not be installed in a bedroom or bath room in the Commonwealth of Massachusetts FP2727 damper Damper Stop Damper FP2727 Figure 3 Damper Stop Installation In compliance with AN...

Page 8: ...ve Pilot Configured for NG Pipe Nipple Heat Shield Knob Extenders SPK LPA Kit Includes Valve Pilot Configured for LP Air Mixing Nut Brass Nut Heat Shield Knob Extenders WARNING LP sets must be install...

Page 9: ...eries Vented Gas Log Set INSTALLATION for gas valve kits LG1052 install pilot Screw Figure 7 Install Pilot LG1052 LG1053 Heat Shield Gas Control Valve Knob Extensions Control Knob LG1053 Figure 8 Inst...

Page 10: ...PLEMENTAL INSTRUCTIONS FOR MVVKNA INSTALLATION for gas valve kits WARNING The MANVK kit is for Natural Gas Only Injector Reducer Valve Knob Extenders Control Knob LG1054 Figure 9 MANVK LP Air Mixing I...

Page 11: ...Bracket Natural Gas Injector Reducer Gas Control Valve Pipe Nipple Burner Fitting Figure 12 CVTHL NG Connect Valve to Unit Natural Gas only Heat Shield Control Knob LG1057 Figure 13 CVTHL LP Connect V...

Page 12: ...a If the reading is more than 100 Millivolts and the automatic valve still does not come on replace the control b If the closed circuit reading A reading is less than 100 Millivolts determine cause fo...

Page 13: ...flow rate BTU Hr Undue pressure loss will occur if the pipe is too small A manual shutoff valve must be installed upstream of the appliance Union tee and plugged 1 8 NPT pressure tapping point should...

Page 14: ...plied with the unit To enhance the ap pearance of the Wildfire flame it is recommended to form a mound of rock wool in the center of the burner 2 to 3 high visible through the logs VWFST18ST and VWF24...

Page 15: ...logs Left Right Curved Log 3 Left Right Curved Log 3 LG1061 Figure 18 LG1062 VWFST charred logs Left Right Split Charred Log 4 Left Right Split Charred Log 4 LG1062 Figure 19 5 Place a left right spli...

Page 16: ...er s instructions If you cannot reach your gas supplier call the fire department B Use only your hand to push in or turn the gas control knob Never use tools If the knob will not push in or turn by ha...

Page 17: ...OFF switch to OFF position 4 Wait five 5 minutes to clear out any gas Then smell for gas including near the floor If you smell gas STOP 5 From OFF position turn the gas control knob counterclockwise...

Page 18: ...B in the safety information label If you don t smell gas go to next step MANUAL CONTROL LIGHTING INSTRUCTIONS FOR YOUR SAFETY READ BEFORE LIGHTING WARNING If you do not follow these instructions exac...

Page 19: ...g fabricating and shipping various components of this appliance are treated with certain oils films or bonding agents These chemicals are not harm ful but may produce annoying smoke and smells as they...

Page 20: ...tes place a match or smoke stick along the top and sides of the fireplace opening If the flame or smoke is not pulled into the fireplace then the fireplace is not venting properly At this point the da...

Page 21: ...y by holding gently at each end Gloves are recommended when handling the log to prevent skin irritation from ceramic fibers If skin becomes irritated wash gently with soap and water Refer to manual fo...

Page 22: ...27D0406 27D7022 27D0406 27D7022 27D0406 2 Manual Control Valve 27D0303 27D8951 27D8951 3 Millivolt Control Valve 27D8006 27D8005 4 Hi Lo Remote Control Valve 27D8954 27D8954 5 Pilot 27D0301 27D0302 20...

Page 23: ...log parts Ref Description Qty VWF18MOST VWF24MOST 1 Bottom Left Front Log 1 2 27D7501 27D7507 2 Bottom Right Front Log 2 2 27D7502 27D7508 3 Left Right Curved Log 3 2 27D8830 27D8581 4 Top Left Right...

Page 24: ...27D8851 24 VWFST Series Vented Gas Log Set...

Page 25: ...25 27D8851 VWFST Series Vented Gas Log Set...

Page 26: ...ly with the above requirements provided however that during said thirty 30 day period a battery operated carbon monoxide detector with an alarm shall be installed Massachusetts Residents Only Please r...

Page 27: ...ns The Limited Lifetime Warranty will also be void if the appliance is not operated and maintained according to the operating instructions supplied with the appliance and does not extend to 1 firebox...

Page 28: ...Vermont Castings Group 149 Cleveland Drive Paris Kentucky 40361 www vermontcastingsgroup com...

Reviews: